KB Electronics KBMK-24DF User Manual
Page 36
36
FIGURE 24
ACCEL/DECEL "2" CONENCTIONS
A4. FORWARD/STOP AND REVERSE/STOP
Remote Forward/Stop and Reverse/Stop operation can be performed by connecting switches or contacts to
the Multi-Function Input Terminals. See Table 17, for drive programming. See Figure 25, for connections.
Connect the Start/Stop Switch or Contact to Multi-Function Input Terminal "5", which is factory set for N.O.
Start ("0010"). Connect the Forward/Stop and Reverse/Stop Switches or Contacts to any Multi-Function Input
Terminals "1" – "7". Terminals "3" and "4" have been arbitrarily chosen for Forward/Stop and Reverse Stop.
Connect the common of the switches or contacts to any available common terminal ("8", "12", "14", "16", "18",
"20", "22").
Operation: When the Forward/Stop Switch or Contact is closed, the drive will run in the forward direction.
When the Forward/Stop Switch or Contact is opened, the drive will stop. When the Reverse/Stop Switch or
Contact is closed, the drive will run in the reverse direction. When the Reverse/Stop Switch or Contact is
opened, the drive will stop.
TABLE 17
FORWARD/STOP-REVERSE/STOP PROGRAMMING
Function No.
Code
1.00: Run/Stop-Forward/Reverse Control 0001:
External Contacts
7.02: Multi-Function Input Terminal 3 0006:
Forward/Stop Command
7.03: Multi-Function Input Terminal 4 0007:
Reverse/Stop Command
7.04: Multi-Function Input Terminal 5
0010: N.O. Start*
FIGURE 25
FORWARD/STOP-REVERSE/STOP CONNECTIONS