KB Electronics KBMK-24DF User Manual
Page 22
22
PROGRAMMABLE FUNCTION SUMMARY LIST (Rev. 100.1)
Model Software Revision Codes (Rev. 100.1)
The Programmable Function List, on Pages 22 – 28, is Applicable to Software Revision Code 14/1.01 (or higher).
PROGRAMMABLE FUNCTION GROUPS
Function
Group No. Description
0
Motor and Drive Parameters
1
Run/Stop Mode
2
Frequency Control
3
Drive Operating Parameters
4
Digital Display Modes
5
Onboard Multi-Function Output Relay Operating Mode
6
Drive Status and Reset
7
Multi-Function Input Terminals
(1)
8
Multi-Function Output Relays and Output Signal Operation
(1)
9
Analog Input Signal Operation
(1)
10
Communication Mode
(2)
Notes: (1) IODA Option Board required. (2) DIAC Option Board required.
FUNCTION GROUP 0 – Motor and Drive Parameters
Function
No. Description
Range/Code
Factory
Setting
0.00 * Rated Motor Frequency (Hz)
0000: 60 Hz
0001: 50 Hz
0002: Special (Set by Function No. 0.05)
0000
0.01 * Motor Nameplate Current (Amps)
—
(1)
0.02 * Motor Type
0000: Inverter Duty, TEFC
0001: External Fan Cooled
0000
0.03 * Torque Mode
0000: Constant Torque (Machinery)
0001: Variable Torque (HVAC)
0000
0.04 * GFCI Operation
(2)
0000: GFCI Operation Disabled
0001: GFCI Operation with Standard GFCI
0002: GFCI Operation with Sensitive GFCI
0000
0.05 * Motor Frequency (Hz)
(3), (4)
30 – 240 60,
50
0.06 *
Motor Nameplate Voltage
(% Drive Output)
(5)
0 – 100.0
100
(6)
Notes: (1) Factory Setting is the drive rated output current. See Table 3, on page 6. This function is used to enter
the Motor Nameplate Rated Current, which allows proper operation of the I
2
t Motor Overload Protection. (2) GFCI
operation overrides the Switching Frequency set by Function No. 3.15. (3) When the drive is set for 50 Hz motors
(Function No. 0.00 set to "0001"), the Motor Frequency factory setting will automatically reset to 50 Hz. (4) The
Motor Frequency for standard 50 Hz or 60 Hz motors is set by Function No. 0.00. For custom motors (e.g., 100 Hz)
set Function No. 0.00 to "0002" and Function No. 0.05 to the Motor Nameplate Rated Frequency. (5) This function
is used for motors with non-standard nameplate rated voltage (e.g., 80 Volts AC). (6) The factory set output of the
drive is 100% of the AC line input voltage. In 60 Hz Mode (Function No. 0.00 set to "0000") the drive output will be
230 Volts, maximum, for 230 Volt motors and 460 Volts, maximum, for 460 Volt motors. In 50 Hz Mode (Function
No. 0.00 set to "0001") the drive output will be 220 Volts, maximum, for 220 Volt motors and 400 Volts, maximum,
for 400 Volt motors.
*Functions which can only be changed while the drive is in the Stop Mode.