TABLE 15
UP/DOWN FREQUENCY CONTROL PROGRAMMING
Function No.
Code/Range
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts
2.00: Frequency Control
0005: Up/Down Using MFITs
7.04: Multi-Function Input Terminal 5 0010:
N.O. Start*
7.05: Multi-Function Input Terminal 6 0003:
Up Frequency Command*
7.06: Multi-Function Input Terminal 7
0004: Down Frequency Command.
7.14: Up/Down Frequency Control Mode 0000: Free-Running 0001: Incremental
7.15: Increment of Up/Down Frequency** 0.01 – 30.00 Hz: Set to Desired Frequency
*Factory setting.
**Use with Function No. 7.14 code "0001" only.
FIGURE 23
UP/DOWN FREQUENCY CONTROL
WITH 2-WIRE START/STOP CONNECTIONS
*Use a jumper, between Terminals "5" and "8", if a Start/Stop Switch
or Contact is not required.
A3. ACCEL/DECEL 2
The drive provides a secondary Accel/Decel Time setting, which can be remotely selected with a normally
open switch or contact connected to a Multi-Function Input Terminal. See Table 16, for drive programming.
See Figure 24, on page 36, for connections.
Connect the Accel/Decel 2 Switch or Contact to any Multi-Function Input Terminal "1" – "7". Terminal "6" has
been arbitrarily chosen for Accel/Decel 2. Connect the common of the switch or contact to any available
common terminal ("8", "12", "14", "16", "18", "20", "22").
Operation: When the Accel/Decel 2 Switch or Contact is closed, the Accel/Decel 2 setting is selected. When
the Accel/Decel 2 Switch or Contact opened, the drive reverts to the Accel/Decel settings in Function Nos.
3.03 and 3.04. Accel/Decel 2 overrides the Accel and Decel settings in Function Nos. 3.03 and 3.04.
TABLE 16
ACCEL/DECEL "2" PROGRAMMING
Function No.
Code/Range
7.05: Multi-Function Input Terminal 6 0005:
Accel/Decel 2
7.16: Accel/Decel 2 Time 0.3
–
180.0:
Set to Desired Time*
*Factory set to 1.5 seconds.