FUNCTION GROUP 1 – Run/Stop Mode
Function
No. Description
Range/Code
Factory
Setting
1.00 * Run/Stop-Forward/Reverse Control
0000: Keypad
0001: External Contacts
(1)
0002: Communication
(2)
0000
1.01 * Forward/Reverse Control
0000: Instant Reverse
0001: Stop Command Must be Given Prior to
Reverse Command
0002: Reverse Command Disabled
0003: Forward Command Disabled
0000
1.02 * Motor Direction
0000: Forward
0001: Reverse
0000
1.03 * Start Command
0000: Accelerates to Last Set Frequency
0001: Accelerates to Lower Frequency Limit
(See Function No. 3.01)
0000
1.04 * Start Mode
0000: Spin Start
0001: Stop Before Restart
0000
1.05 * Auto/Manual Start Mode
0000: Manual Start Mode
0001: Manual Start with Ride-Through
(Set by Function No. 1.06)
0002: Auto Start After Undervoltage Fault Clears
0003: Auto Start All Faults
(Except Short Circuit Fault)
(3)
0004: Auto Start All Faults
(Except I
2
t, I•t, and Short Circuit Faults)
0000
1.06 * Ride-Through Time (Seconds)
0.0 – 2.0
0.5
1.07 * Number of Restart Attempts
0 – 10
3
1.08 * Start Delay Time (Seconds)
0 – 240
0
1.09 * Stop Mode
0000: Regenerate-to-Stop
0001: Coast-to-Stop
0002: Regeneration with Injection Brake-to-Stop
(Set by Function Nos. 1.11 – 1.13)
0000
1.10 * Holding Torque in Stop Mode (%)
0 – 10
1
1.11
Injection Brake Start Frequency (Hz)
0.00 – 240.0
0.00
1.12
Injection Brake Level (%)
0 – 30
0
1.13
Injection Brake Time (Seconds)
0.0 – 25.5
0.0
Notes: (1) IODA Option Board required. (2) DIAC Option Board required. (3) For Auto Start, Function No. 1.07
must be set to greater than "0".
*Functions which can only be changed while the drive is in the Stop Mode.