IAI America ACON-CY User Manual
Page 73

61
5. Operation Using I/O Signals
Full-scale Operation
In situations where the actuator remains standstill for a long time at a standby position, this controller provides a
mode to reduce power consumption in such standstill state as part of the controller’s energy-saving function.
You can also select the positioning complete signal state to be applied when the servo turns off or “position
deviation” occurs while the actuator is standing still after completion of positioning.
Use these modes after confirming that they will not cause problems in any part of the system.
Power-saving when the standby time at the target position is long
In this case, you can select the desired mode based on the value set in the “Standstill mode” field of the
position table.
(The setting of Parameter No. 53 is ignored.)
o For details, refer to 5.4, “Power-saving Mode at Standby Positions” and 6.2.2, “Parameters Relating to
Actuator Operating Characteristics.”
Complete signal output mode
You can select the positioning complete signal state to be applied when the servo turns off or “position
deviation” occurs while the actuator is standing still after completion of positioning.
This setting uses Parameter No. 39. Select an appropriate mode by considering the characteristics of the
specific control.
o For details, refer to 6.2.3, “Parameters Relating to External Interface.”