IAI America ACON-CY User Manual
Page 62

50
5. Operation Using I/O Signals
5.2.4 Homing
This controller adopts an incremental position detector (encoder), so once the power is cut off, the mechanical
coordinates will be lost.
Accordingly, homing must be performed to establish the initial mechanical coordinate every time the power is
turned on.
To perform homing, input a rear end move command (ST0).
Operation timings
PLC processing 1: The rear end move command signal (ST0) turns ON when the start button is pressed.
Operation:
[1] The actuator starts moving toward the mechanical end on the home side.
[2] After contacting the mechanical end, the actuator reverses its direction and
temporarily stops at the home position.
o The homing complete signal (HEND) turns ON.
[3] The actuator moves toward the rear end, and stops at the rear end.
o The rear end detection output (LS0) turns ON.
PLC processing 2: The rear end move command signal (ST0) turns OFF.
PLC processing 3: The actuator starts continuous operation.
Caution:
Take note of the following points regarding homing:
[1] Confirm that no obstacle exists between the actuator and the rear end.
[2] If an obstacle exists between the actuator and the rear end, move the actuator toward the
front end and remove the obstacle. The controller accepts a front end move command prior
to homing to accommodate the aforementioned condition.
In this case, the actuator moves forward at the homing speed and once the mechanical end
is reached, the front end detection output (LS1) will turn ON.
This LS1 signal should be recognized as a tentative signal.
[3] Do not input an intermediate move command. (Even if an intermediate move command is
input, it will be ignored.)
Rear end move command
input (ST0)
Homing complete
output (HEND)
Rear end detection output
(LS0)
Power-
on pos
ition
Mechanical end
Home position
Rear end
Max. 6 msec
[1]
[2]
[3]