Code Message
Description
20C
CSTR-ON during operation A move command signal from the PLC turned ON while the actuator was
moving, resulting in redundant move commands.
20E
Soft limit over
A soft limit was reached.
221
Write inhibited in monitor
mode
A position table field or parameter was written in the monitor mode.
223
Operation inhibited in
monitor mode
The actuator was moved in the monitor mode.
301
302
304
305
306
308
30A
30B
Overrun error (M)
Framing error (M)
SCIR-QUE OV (M)
SCIS-QUE OV (M)
R-BF OV
Response timeout (M)
Packet R-QUE OV
Packet S-QUE OV
An error occurred in serial communication with the controller.
Cause: [1] Garbage data due to noise
[2] Duplicate slave numbers when multiple actuators are
controlled via serial communication
Action: [1] Revise the wiring, equipment layout, etc., to eliminate noise.
[2] Change the slave numbers to eliminate duplication.
If the message persists, please contact IAI.
307
Memory command denied A command was denied in serial communication with the controller.
309
Write address error
An indeterminable write address error occurred in serial communication
with the controller.
These messages do not generate during normal operation. Should either
of them occur, record the entire error list before turning off the power. The
recorded error list will help us identify the cause of the problem.
Also contact IAI.
30C
No connected axis
The controller axis number cannot be recognized.
Cause: [1] The controller is not operating properly.
[2] Only the communication line of the supplied cable
(SGA/SGB) is open.
[3] If the SIO converter is used, the link cable is not connected
although the converter is receiving 24 V.
[4] When multiple controllers are linked, the ADRS switch is set
to the same number by mistake on two or more controllers.
Action: [1] Check if the RDY LED on the controller is lit. If this LED is
not lit, the controller is faulty.
[2] If you have a spare teaching pendant, change to the spare
teaching pendant. Or, switch to the PC software mode and
see if the message will disappear.
[3] Connect all pairs of converter and controller using link
cables, and then supply the power.
[4] Set each ADRS switch to a unique number.
If the message persists, please contact IAI.