28
3. Installation and W
iring
Use an SIO converter if it is desired to stop the entire system urgently by emergent stop via the teaching pendant.
The operation on the emergency stop switch of the teaching pendant can also be reflected when a gateway unit is
used as well.
Precautions on power supply and emergency stop circuit
*1 Refer to the specification list for the load current conducted per controller.
*2 The input current to the EMG- terminal per controller is 5 mA. When connecting a relay contact CR to
EMG- terminals of several controllers, make sure to check the capacity of the relay contact.
*3 When the teaching pendant is inserted to a controller, the controller automatically recognizes that it is
connected.
EMG signal
detection (H)
Time
constant
Drive stop signal (L)
Motor
drive
circuit
External
EMG
reset
switch
External
EMG
circuit
Motor
power
supply
Controller
power supply
Controller 2
Controller n
Under normal
circumstances, it
is jumpered. If the
safety category
requires shutting
down motor
driving source,
use the following
circuit (the same
timing as EMG).
The brake is turned
on/off automatically
by turning on/off of
the servo. To
release the brake
manually, close the
brake release
switch.
* The brake release
switch shall be
prepared by the
customer.
(Switch)
24 VDC
Contact capacity
0.2 A or higher
Port switch
SIO
connector
Connection
detection
circuit
Brake release
switch
EMG switch of
teaching pendant
SIO
communication
EMG switch of
teaching pendant
Port switch