X501NET System Configuration Manual © 2008 Ronan Engineering Company 24

Status Enabled

Card in Slot

Configured and missing

checked no

Not Available

not checked

no

2.7.2.6 Test Field

The Test field allows input card test to be enabled

23

(field checked) or disabled (field not

checked) on an individual card basis.

2.7.2.7 Interval Field

The Interval field allows interval between tests card test to be assigned

24

on an individual card

basis.

Regardless that it is possible to assign an individual loop test interval for each card, in most cases
it is preferred to use single and same for all cards intervals. By setting Global Loop Test interval
to a number different than 0 the individual intervals are disregarded

2.8 Points Configuration Page

The Points Configuration page provides a means to view and/or configure the
parameters of each input point of the X501NET, as well as a means to navigate through the
points.

23

Not all input cards (e.g. X501-307N) have hardware capabilities for performing this test. If a is enabled and the

card can not perform the test, the test will not be run on the card.

24

Although that it is possible to assign an individual loop test interval for each card, in most cases it is preferred to

use single and same for all cards intervals. If the Global Test Interval to a value different than 0 the individual
Intervals are disregarded.