SPECIFICATIONS

Inputs

• Zirconia oxygen probe, heated or unheated
• Furnace, kiln or flue thermocouple, field selectable as type K or R.
• Main flame established safety interlock (for heated probes only)
• Purge pressure switch
• Dual Fuel selector

Remote alarm accept

Outputs

• Two linearised 4 to 20 mA DC outputs, max. load 1000Ω
• Common alarm relay

Three other alarm relays with selectable functions

Computer

• RS 232-C or RS 485 for connection of a computer terminal or printer for diagnostics of

the transmitter, probe, sensor or combustion process. This connection is suitable for
network connection to computers, DCSs or PLCs using

MODBUS protocol.

Range of Output 1

Field selectable from the following:
Output Selection

Range

Linear, Probe 1

0 to 1% oxygen to 0 to 100 % oxygen

Linear, Probe 1 and 2 averaged 0 to 1% oxygen to 0 to 100 % oxygen
(If 2 probes are used)
Log

0.1 to 20 % oxygen, fixed

Reducing

100 % to 10-4 oxygen, fixed

Reducing 10-1 to 10-25 % oxygen, fixed
Linear, probe 1, very low range 0 to 0.001% to 0 to 2.0 % oxygen (10ppm to 20,000ppm)

Range of Output 2
Field selectable from the following:
Output

Zero Range

Span Range

Sensor EMF

0 to 1100 mV in 100 mV steps

1000 to 1300 mV in 100

mV

steps

Carbon Dioxide

0 to 10 %

2 to 20 %

Oxygen Deficiency

0 to 20% O2 deficiency

0 to 100% O2 excess

Aux Temperature

0 to 100°C (32 to 210°F) in 1 degree steps

100 to 1400°C (210 to

2550°F) in 100 degree

steps

Log Oxygen

0.1% O2 Fixed

20% O2 Fixed

Reducing Oxygen

10+2 (100%) to 10-10 % oxygen in one

10-3 to 10-30 % oxygen

decade steps, non-overlapping

in one decade steps. Min

span two decades.

Linear Oxygen, probe 2

0% oxygen, fixed

1 to 100%


Combustibles %, Probe 1

0% combustibles fixed

0.5 to 2.0 %

Linear, Probe 1 and 2 averaged

0% oxygen, fixed

1 to 100%

(If 2 probes are used)