beautypg.com

GF Signet 8850 ProcessPro Conductivity-Resistivity Transmitter User Manual

Page 2

background image

2

8850-3 Conductivity/Resistivity Transmitter

14
13
12
11

Shield (Sensor Gnd)
Black (Iso Gnd)
White (Temp In)
Red (Signal In)

Signet 28XX-1

Standard and Certified Cells

Terminals

3.1 Sensor Input Connections

≤ 30 m (100 ft)

Signet

Conductivity/Resistivity

Transmitter

ENTER

62.50 uS/cm

25.0 C

Sensr Gnd

(SHIELD)

Iso. Gnd

(BLACK)

Temp. IN

(WHITE)

Signal IN

(RED)

14

13

12

11

Output 2-

Output 2+

Output 1-

Output 1+

10

9

8

7

Loop 2-

Loop 2+

System Pwr

Loop -

System Pwr

Loop +

AUX

Power -

AUX

Power +

6

5

4

3

2

1

3. Electrical

Connections

Caution:

Failure to fully open terminal jaws before removing wire may permanently damage instrument.

Wiring Procedure
1. Remove 0.5 to 0.625 in. (13 to16 mm) of insulation from wire end.
2. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
3. Insert exposed (non-insulated) wire end in terminal hole until it bottoms out.
4. Release orange terminal lever to secure wire in place. Gently pull on each wire to ensure a good connection.

Wiring Removal Procedure
1. Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
2. When fully open, remove wire from terminal.

Wiring Tips:
• Do not route sensor cable in conduit containing AC power wiring. Electrical noise may interfere with sensor signal.
• Routing sensor cable in grounded metal conduit will help prevent electrical noise and mechanical damage.
• Seal cable entry points to prevent moisture damage.
• Only one wire should be inserted into a terminal. Splice double wires outside the terminal.

2
1

Terminals 7-10: Open-collector Outputs
• Two transistor outputs, programmable as:

• High or Low setpoint with adjustable hysteresis

• Proportional Pulse (to 400 pulses per minute maximum)

• May be disabled (Off) if not used

Terminals 3–6: Loop Power
12 to 24 VDC ±10% system power

and current loop output.

Max. loop impedance:

50

 max. @ 12 V

325

 max. @ 18 V

600

 max. @ 24 V

Terminals 11–14: Sensor Input
11 is conductivity input
12 is temperature input
13 is the isolated signal ground
14 is the sensor earth ground

Terminals 1–2: Auxiliary power
Provides DC power to measurement
circuit. Required for all 8850 systems

1

Internal open-collector

output circuit

Outputs

Isolation

15 Ω

S

D

2

_

+