Technical data – Burkert Type 8035 User Manual
Page 7

7
Technical data
Type 8025/8035 /
6.
TechnicAl DATA
The following technical data are relevant for a 8025 compact or a
8035 and for the remote 8025 connected to a Bürkert flow sensor
8020 / 8030 in a "Low Power" version only.
6.1.
conditions of use
Ambient temperature
• 8025 compact, 115/230 V AC,
not UR or CSA recognized
• 8035 compact, 115/230 V AC,
not UR or CSA recognized
• other versions, not UR or CSA
recognized
• UR and CSA recognized
versions
• -10 to 50 °C
• -10 to 50 °C
• -10 to 60 °C
• -10 to 40 °C
Air humidity
< 80%, non condensated
Degree of pollution (UR and CSA
recognized versions)
Degree 2 according to EN
61010-1
Installation category (UR and CSA
recognized versions)
Category I according to
UL61010-1
Max. height above sea level
2000 m
Protection rating
• 8025 compact and 8035
• 8025 wall-mounted
• Housing, panel version
• non front parts, panel-mounted
version
According to EN 60529
• IP65, device wired and
cable glands tightened and
cover lid screwed tight.
• IP65, device wired, cable
glands tightened, cover lid
screwed tight and entry
item nuts of the cable
glands tightened at a
screwing torque of 1.5 Nm.
• IP65, installation com-
pleted and closed cabinet
• IP20
6.2.
conformity to standards and
directives
The device conforms to the EC directives through the following
standards:
• EMC: EN 61000-6-2, EN 61000-6-3, EN 550022
• LVD: EN 61010-1
• Environnemental testing: Vibration: EN 60068-2-6, Shock:
EN 60068-2-27.