Installation
Type 8025/8035 /
7.
insTAllATion
7.1.
safety instructions
danger
risk of injury due to electrical voltage.
• Shut down the electrical power source of all the conductors and
isolate it before carrying out work on the system.
• Observe all applicable accident protection and safety regulations for
electrical equipment.
Warning
risk of injury due to non-conforming installation.
• The electrical and fluid installation can only be carried out by quali-
fied and skilled staff with the appropriate tools.
• Install appropriate safety devices (correctly rated fuse and/
or circuit-breaker); for the versions with 115/230 V AC power
supply, insert a protection device between phase and neutral.
• Respect standard NF C 15-100 / IEC 60364.
• Observe mounting instructions of the fitting.
risk of injury due to unintentional switch on of power supply
or uncontrolled restarting of the installation.
• Take appropriate measures to avoid unintentional activation of the
installation.
• Guarantee a set or controlled restarting of the process subse-
quent to any intervention on the device.
6.7.
electrical connection
Version
Wiring features
With male fixed
connector
Female connector (type 2508 supplied)
For the female connector type 2508 with
order code 438811 and the female con-
nector type 2509 (not supplied) with order
code 162673, use a shielded cable.
• external diameter of the cable: 5 to 8 mm
• cross section of the wires: 0.2 to
1.5 mm
2
• max. length of the power supply, current
output and pulse output connection
cables: 50 m
With terminal strip,
with or without cable
glands
Shielded cable (not supplied):
• external diameter of the cable: 6 to
12 mm (4 to 6 mm when using a mul-
tiway seal)
• cross section of the wires: 0.2 to
1.5 mm
2
All
Cross section of the local earthing wire:
0.75 mm
2