English – Burkert Type 8035 User Manual
Page 36

36
Wiring
Type 8025/8035 /
8.4.6. Wiring the 8025 compact version and the 8035, 115/230V Ac, without relays, with
cable glands
→
Before wiring the device, configure the selectors on the electronic board (see chap. "8.3").
Supply
12..36Vdc
FLOW SENSOR
COIL
NPN
SOURCE SINK
L+
L-
PE
P-
P+
NC
L+
L-
PE
P-
P+
Iout
PULSE
OUTPUT
Without
With
Relays
N
PE
L
230V
T 125 mA
{
3
7
8
9
6
5
4
A
2
1
B
C
PE
Switch A : see chap. "8.3.1"
Switch B : see chap. "8.3.3"
Switch C : see chap. "8.3.2"
terminal block 1
lout: 4-20 mA output
L+ (red wire, factory wired)
L- (black wire, factory wired)
PE: wiring of the PE between the main board and the protection board
P-: negative pulse output
P+: positive pulse output
terminal block 2 pe
Shield connection (green/yellow wire, factory wired)
connector 3: connection of the flow sensor
terminal block 4: wiring of relay 1, see chap. "8.4.2"
terminal block 5: wiring of relay 2, see chap. "8.4.2".
Jumper wire 6: jumper wire to be removed if the 4-20 mA output is
connected
time-delay fuse 7: fuse to protect the 115 V AC or 230 V AC
power supply
terminal 8: earth terminal, internally connected to the earth plug
terminal block 9: wiring of the 115/230 V AC power supply
Fig. 32: Terminal assignment of a 115/230 V AC compact version, with relays, with cable glands
English