beautypg.com

Configuring the selectors, Flow sensor selector, Source/sink selector – Burkert Type 8035 User Manual

Page 25: English, Fig. 19: position of the source / sink selector

background image

25

Wiring

Type 8025/8035 /

8.3.

configuring the selectors

Only move the selectors when the power supply is off.

Before wiring the device, configure the selectors on the elec-
tronic board. See chap. "8.3.1" to "8.3.3".

8.3.1. floW sensor selector

The FLOW SENSOR selector makes it possible to configure the
type of flow sensor: coil or Hall.

For the version with male fixed connector, the selector
is factory-set depending on the output signal of the flow
sensor mounted on the device.

Supply

12..36Vdc

FLOW SENSOR

COIL

NPN

L+

L-

PE

P-

P+

NC

L+

L-

PE

P-

P+

Iout

PULSE

OUTPUT

Without

With

Relays

FLOW SENSOR

COIL

NPN

PE

Fig. 18: Position of the FLOW SENSOR connector on the

electronic board

Table 2: Positioning of the FLOW SENSOR selector depending on

the output signal of the flow sensor

Version of the
flowmeter

output signal of
the remote sensor

position of the floW
sensor selector

All

Pulse, NPN (hall)

NPN

All

Sinus (coil)

COIL

8.3.2. source/sink selector

The Source/Sink selector makes it possible to set the 4-20 mA
current output of the versions with relays, in sourcing or in sinking
mode. Set the selector depending on the type of wiring.

Supply

12..36Vdc

FLOW SENSOR

COIL

NPN

SOURCE SINK

L+

L-

PE

P-

P+

NC

L+

L-

PE

P-

P+

Iout

PULSE

OUTPUT

Without

With

Relays

SOURCE SINK

Without

Relays

PE

Fig. 19: Position of the Source / Sink selector

English