Wiring

Type 8025/8035 /

terminal block 1
Iout: 4-20 mA output (green wire, factory wired)
L+ (red wire, factory wired)
L- (black wire, factory wired)
PE: wiring of the PE between the main board and the protection board
P-: (brown wire, factory wired)
P+: (white wire, factory wired)
terminal block 2 pe: Shield wiring (green/yellow wire, factory wired)
time-delay fuse 3: fuse to protect the 115 V AC or 230 V AC power supply
terminal block 4: wiring of the 115/230 V AC power supply
Jumper wire 5: jumper wire to be removed if the 4-20 mA output is connected
terminal block 6
Terminal 5: 4-20 mA output
Terminal 6: positive 27 V DC power supply, available to energize an external instrument
Terminal 7: 0V (earth of the power supply available to energize an external instrument)
Terminal 8: cable shields
Terminal 9: negative pulse output
Terminal 10: positive pulse output
marker 7: all the cables must be fitted here
terminal block 8: wiring of relays 1, see chap. "8.4.2"
terminal block 9: wiring of relays 2, see chap. "8.4.2"
connector 10: connection of the flow sensor

Fig. 44: Terminal assignment of a wall-mounted version, 115/230 V AC, with relays