Series 6A Operation & Maintenance – Technical Data

6A O & M : 36

Technical specifications

SIPART PS2

Basic device

without Ex protection

Basic device

with Ex d protection

(flameproof enclosure)

Basic device

with Ex ia/ib protection

Basic device

with Ex n/

dust protection

Explosion protection ATEX

-

Ex d

II 2 G Ex d II C T6

Ex ia/ib

II 2 G Ex ia/ib II C T6

Ex n

II 3 G Ex nA nL[nL] IIC T6
Dust

II 3 D Ex tD A22 IP66

T100°C

Mounting location

-

Zone 1

Zone 2/22

Permissible ambient temperature for

operation
At ≤ -10 °C (+14 °F) the display refresh

rate of the indicator is limited.
(for basic devices with EX ia/ib and Ex n

protection the following applies: Only T4

is permissible when using I

y

module)

-30 ... +80 °C

(-22 ... +176 °F)

T4: -30 ... +80 °C (-22 ... +176 °F)

T5: -30 ... +65 °C (-22 ... +149 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)

Electrical specifications
Input
2-wire connection (terminals 6/8)
Rated signal range

4 ... 20 mA

Current to maintain the auxiliary power

supply

≥ 3.6 mA

Required load voltage

U

B

(corresponds to Ω at 20 mA)

• Without HART (6DR50..)

- Typical

6.36 V

(corresponds to 318 Ω)

7.8 V

(corresponds to 390 Ω)

- max.

6.48 V

(corresponds to 324 Ω)

8.3 V

(corresponds to 415 Ω)

• Without HART (6DR53..)

- Typical

7.9 V

(corresponds to 395 Ω)

- max.

8.4 V

(corresponds to 420 Ω)

• With HART (6DR51..)

- Typical

6.6 V

(corresponds to 330 Ω)

- max.

• With HART (6DR52..)

- Typical

8.4 V

(corresponds to 420 Ω)

- max.

8.8 V

(corresponds to 440 Ω)

• Static destruction limit

± 40 mA

Internal capacitance C

i

• Without HART

22 nF

22 nF (at "nL")

• With HART

7 nF

7 nF (at "nL")

Internal inductance L

i

• Without HART

0.12 mH

0.12 mH (at "nL")

• With HART

0.24 mH

0.24 mH (at "nL")

For connection to circuits with the fol-

lowing peak values

intrinsically safe

U

i

= 30 V DC

I

i

= 100 mA

P

i

= 1 W

at "nA" and "tD":

U

n

= 30 V DC

I

n

= 100 mA

at "nL":

U

i

= 30 V DC

I

i

= 100 mA