beautypg.com

Factory or field installable options – Bray 6A Series O&M Manual User Manual

Page 20

background image

All information herein is proprietary and confidential and may not be copied or reproduced without the expressed written consent of BRAY INTERNATIONAL, Inc.

The technical data herein is for general information only. Product suitability should be based solely upon customer’s detailed knowledge and experience with their application.

Series 6A Operation & Maintenance – Installable Options

6A O & M : 20

fACTOry Or fIelD InSTAllAble OpTIOnS

The S6A comes standard with guides beneath the motherboard so

that optional modules can be added.
Tools Needed:

• T2O Torx

• Phillips Screwdriver

Step A
To install any of the optional modules proceed as follows:

1. Disconnect electrical power from the supply to the positioner
2. Remove pressure from the pneumatic supply lines to the

positioner.

3. Remove the positioner cover by loosening the 4 screws using

the Phillips screwdriver.

4. Remove the module cover by loosening the 2 screws using the

T20 torx drive.

Note: Step A must be performed before installing any of the

modules.

Installing the Feedback Module (Iy Module)

Feedback Module (ly Module)

Function
The optional Iy module indicates the current actuator position as a

dual line signal with Iy = 4 to 20 mA. The Iy module is potentially

isolated from the standard controller. Due to the dynamic control,

this module can report the arising operational faults automatically.

Device features
The Iy module is:

• Single channel
• Potentially isolated from the standard controller.

Note: The current actuator position is indicated only after a suc-

cessful initialization of the positioner. [Refer to the “Calibration

and Commissioning” section]

Proceed as follows to install the optional Iy module:

1. Perform Step A to remove the module cover
2. Slide the Iy module up to the end stop in the lower stack of the

module rack.

3. Connect the module to the motherboard. For this purpose, use

the 6-pole flat ribbon cable provided.

4. Refer to Figure 8 and Figure 9 to connect the Iy module in

standard and intrinsically safe applications.

≤ 30 V

E

U

H

I

y

module

6DR4004-6J

Non-hazardous area

Intrinsically safe

power source

Hazardous area, Zone 1 or zone 2

EEx

+

+

I

+

I

U

Ammeter

Figure 8

-

Iy

module 6DR4004-8J, not Ex

61
62

≤ 35 V

+

E

I

I

y

module

6DR4004-8J

I

y

module 6DR4004-8J, not Ex

+

UH

Current Meter
(Ammeter)

Figure 9

-

Iy module 6DR4004-6J, EEx i