Bray 6A Series O&M Manual User Manual
Page 18
All information herein is proprietary and confidential and may not be copied or reproduced without the expressed written consent of BRAY INTERNATIONAL, Inc.
The technical data herein is for general information only. Product suitability should be based solely upon customer’s detailed knowledge and experience with their application.
Series 6A Operation & Maintenance – Calibration & Commissioning
6A O & M : 18
53) FSTI
Monitoring Period for
setting the safety seating
0 … 100
(s). Once this set value expires the positioner
switches to its safety position. (Factory defined at 0)
54) FSVL
Safety Setpoint
0.0 … 100.0
(%). Default value of the safety position. (Factory
setting is 0%)
55) STNR
Station Number
0 … 126
Independent value for each station. (Default position
is 126)
0
Profile Compliant. Can be replaced with other
positioners complying with Profibus PA profile 3.0
56) IDENT
Device operating mode
(ID No.)
1
Compliant with Extensions (Factory Defined).
Parameter
Function
Parameter Values
Description
A. PST
Partial Stroke Test
Used to activate the partial stroke test for cyclic or
manual test of up/down and servo solenoid valves.
A1.STPOS
Starting position
0.0 … 100.0
Start position in %. Factory setting is “100.0”
A2.STTOL
Starting tolerance
0.1 … 2.0 … 10.0
Start position tolerance in %. Factory setting is
“2.0”
A3.STEP
Step height
0.1 ..10.0 ..100.0
Step height of partial stroke test in %
A4.STEPD
Step Direction
uP / do / uP do
Step direction of partial stroke test. Factory setting
is “do”
A5.INTRV
Test Interval
OFF / 1 … 365
Interval time for cyclic partial stroke in days. “Off”
A6.PSTIN
Partial Stroke ref. step time
NOINI / (C) ###.# /
Fdini / rEAL
Reference step time for partial stroke in s. “NOINI”
A7.FACT1
Factor 1
0.1 … 1.5 … 100.0
Factor for the formation of limit threshold 1. “1.5”
A8.FACT2
Factor 2
0.1 … 3.0 … 100.0
Factor for the formation of limit threshold 2. “3.0”
A9.FACT3
Factor 3
0.1 … 5.0 … 100.0
Factor for the formation of limit threshold 3. “5.0”
b. DEVI
General Control Valve Fault
Test for dynamic monitoring of control valve
response.
b1.TIM
Time constant
Auto / 1 … 400
Defines the attenuation effect of the low-pass filter.
“Auto”
b2.LIMIT
Limit
0.1 … 1.0 … 100.0
Sets a base limit in %. “1.0”
b3.FACT1
Factor 1
0.1 … 5.0 … 100.0
Factor for the formation of limit threshold 1. “5.0”
b4.FACT2
Factor 2
0.1 ..10.0..100.0
Factor for the formation of limit threshold 2. “10.0”
b5.FACT3
Factor 3
0.1..15.0..100.0
Factor for the formation of limit threshold 3. “15.0”
C. LEAK
Pneumatic leakage
Activates the pneumatic leakage test
C1.LIMIT
Limit
0.1 .. 30.0 .. 100.0
Sets the limit of the leakage indicator in %. “30.0”
C2.FACT1
Factor 1
0.1 … 1.0 … 100.0
Factor for the formation of limit threshold 1. “1.0”
C3.FACT2
Factor 2
0.1 … 1.5 … 100.0
Factor for the formation of limit threshold 2. “1.5”
C4.FACT3
Factor 3
0.1 … 2.0 … 100.0
Factor for the formation of limit threshold 3. “2.0”
d. STIC
Friction (slip-stick effect)
Monitors the current static friction of the final
controlling element
d1.LIMIT
Limit
0.1 … 1.0 … 100.0
Sets the base limit for the slipstick detection in %.
“1.0”
d2.FACT1
Factor 1
0.1 … 2.0 … 100.0
Factor for the formation of limit threshold 1. “2.0”
d3.FACT2
Factor 2
0.1 … 5.0 … 100.0
Factor for the formation of limit threshold 2. “5.0”
d4.FACT3
Factor 3
0.1 ..10.0..100.0
Factor for the formation of limit threshold 3. “10.0”
E. DEBA
Dead zone monitoring
Used to measure the automatic adjustment of the
dead zones
e1.LEVEL3
Threshold
0.1 … 2.0 … 10.0
Sets the factor limit threshold to monitor the dead
zone adjustment