Series 6A Operation & Maintenance – Calibration & Commissioning

6A O & M : 18

53) FSTI

Monitoring Period for

setting the safety seating

0 … 100

(s). Once this set value expires the positioner

switches to its safety position. (Factory defined at 0)

54) FSVL

Safety Setpoint

0.0 … 100.0

(%). Default value of the safety position. (Factory

setting is 0%)

55) STNR

Station Number

0 … 126

Independent value for each station. (Default position

is 126)

0

Profile Compliant. Can be replaced with other

positioners complying with Profibus PA profile 3.0

56) IDENT

Device operating mode

(ID No.)

1

Compliant with Extensions (Factory Defined).

Parameter

Function

Parameter Values

Description

A. PST

Partial Stroke Test

Used to activate the partial stroke test for cyclic or

manual test of up/down and servo solenoid valves.

A1.STPOS

Starting position

0.0 … 100.0

Start position in %. Factory setting is “100.0”

A2.STTOL

Starting tolerance

0.1 … 2.0 … 10.0

Start position tolerance in %. Factory setting is

“2.0”

A3.STEP

Step height

0.1 ..10.0 ..100.0

Step height of partial stroke test in %

A4.STEPD

Step Direction

uP / do / uP do

Step direction of partial stroke test. Factory setting

is “do”

A5.INTRV

Test Interval

OFF / 1 … 365

Interval time for cyclic partial stroke in days. “Off”

A6.PSTIN

Partial Stroke ref. step time

NOINI / (C) ###.# /

Fdini / rEAL

Reference step time for partial stroke in s. “NOINI”

A7.FACT1

Factor 1

0.1 … 1.5 … 100.0

Factor for the formation of limit threshold 1. “1.5”

A8.FACT2

Factor 2

0.1 … 3.0 … 100.0

Factor for the formation of limit threshold 2. “3.0”

A9.FACT3

Factor 3

0.1 … 5.0 … 100.0

Factor for the formation of limit threshold 3. “5.0”

b. DEVI

General Control Valve Fault

Test for dynamic monitoring of control valve

response.

b1.TIM

Time constant

Auto / 1 … 400

Defines the attenuation effect of the low-pass filter.

“Auto”

b2.LIMIT

Limit

0.1 … 1.0 … 100.0

Sets a base limit in %. “1.0”

b3.FACT1

Factor 1

0.1 … 5.0 … 100.0

Factor for the formation of limit threshold 1. “5.0”

b4.FACT2

Factor 2

0.1 ..10.0..100.0

Factor for the formation of limit threshold 2. “10.0”

b5.FACT3

Factor 3

0.1..15.0..100.0

Factor for the formation of limit threshold 3. “15.0”

C. LEAK

Pneumatic leakage

Activates the pneumatic leakage test

C1.LIMIT

Limit

0.1 .. 30.0 .. 100.0

Sets the limit of the leakage indicator in %. “30.0”

C2.FACT1

Factor 1

0.1 … 1.0 … 100.0

Factor for the formation of limit threshold 1. “1.0”

C3.FACT2

Factor 2

0.1 … 1.5 … 100.0

Factor for the formation of limit threshold 2. “1.5”

C4.FACT3

Factor 3

0.1 … 2.0 … 100.0

Factor for the formation of limit threshold 3. “2.0”

d. STIC

Friction (slip-stick effect)

Monitors the current static friction of the final

controlling element

d1.LIMIT

Limit

0.1 … 1.0 … 100.0

Sets the base limit for the slipstick detection in %.

“1.0”

d2.FACT1

Factor 1

0.1 … 2.0 … 100.0

Factor for the formation of limit threshold 1. “2.0”

d3.FACT2

Factor 2

0.1 … 5.0 … 100.0

Factor for the formation of limit threshold 2. “5.0”

d4.FACT3

Factor 3

0.1 ..10.0..100.0

Factor for the formation of limit threshold 3. “10.0”

E. DEBA

Dead zone monitoring

Used to measure the automatic adjustment of the

dead zones

e1.LEVEL3

Threshold

0.1 … 2.0 … 10.0

Sets the factor limit threshold to monitor the dead

zone adjustment