beautypg.com

Bray Cryogenic User Manual

Bray Equipment

background image

Installation and Maintenance Manual

Multiport Threaded and Weld End Ball Valves

Date: August 2011 / Page 1 of 6

®

A Subsidiary of BRAY INTERNATIONAL, Inc.

FLOW-TEK, Inc.

Tel: 832.912.2300

© 2011 Flow-Tek, Inc.

8323 N. Eldridge Pkwy #100

Fax: 832.912.2301

Houston, Texas 77041

www.flow-tek.com

CRYOGENIC AND LOW TEMPERATURE SERVICE

TRIAD SERIES BALL VALVES

(FP2000/FP3000 and SP2000/SP3000 WITH CRYO OR LOW TEMP EXTENSION)

INSTALLATION - MAINTENANCE MANUAL

DESIGN
The extended stem assembly is designed to remove

the packing components and actuation from the cold

environment.

The three piece valve assembly allows for ease of

maintenance without special tools. These valves

feature a “free floating” ball. The ball is not fixed, but

is free to move with the line pressure. All valves are

provided with a vented ball and the flow direction

is indicated with an arrow. These valves should be

installed with the vented side of the ball upstream.

The valve is unidirectional in this configuration.

The downstream seat, opposite the pressurized side

of a closed valve, carries the load exerted by the

line pressure on the ball, while the upstream seat is

subject to little load or wear.

1. USE
The valve should be maintained as part of a

preventative maintenance program and in accordance

with Flow-Tek’s recommended pressure, temperature

and corrosion limits to ensure a long service life.

During shipment, storage, and in operation, the valve

should be fully open (“open” is preferred for shipping

and storage). Do not use in throttling service without

investigating flow and pressure conditions.

WARNING: Before installing this equipment, confirm

that it is suitable for the intended service.

The identifications tags describe the maximum

allowable service conditions for this product.

Be sure that the installation is protected by appropriate

pressure control and safety devices to ensure that

acceptable limits are not exceeded.

2. OPERATION:
Operation of the valve is done by turning the handle

a 1/4 turn (90 degree turn). Clockwise to close,

counter-clockwise to open.

A. VALVE OPEN POSITlON
The handle is parallel with the pipeline.

B. VALVE IN CLOSED POSITION
The handle is perpendicular to the pipeline.

Valves with actuators should be checked for actuator

-valve alignment. Misalignment will result in high

operational torque and damage to valve stem and seals.

3. STEM SEAL ADJUSTMENT:
1. For 1/2”- 2”, if slight leakage is noted at stem,

straighten lock washer tab, tighten stem nut to

flatten Bellville Washers, back stem nut off 1/4

turn, secure lock washer tab.

2. For sizes larger than 2”, simply tighten gland

bolts evenly until leak stops. Do not over tighten.

4. GENERAL INFORMATION FOR ON-SITE

INSTALLATION:
The valve must be installed in a horizontal piping run

with the stem vertical within +/- 25 degrees.

Before installing the valves, the pipes must be flushed

clean of dirt, burrs, and welding residues, or the

seats and ball surface will be damaged. See sections

9 thru 11 for installation details. Note direction of

flow arrow.

5. DISASSEMBLY & CLEANING PROCEDURES:
CAUTION: Line must be depressurized before

disassembly. Valve should be cycled to assure there is

no pressure is trapped in valve cavity. Ball valves can

trap pressurized media when closed. Flush line with

valve 1/2 open to remove hazardous media.

WARNING: DO NOT remove packing gland or any