Series 6A Operation & Maintenance – Technical Data

6A O & M : 33

Technical specifications

SIPART PS2 FF

Basic device

without Ex protection

Basic device

with Ex d protection

(flameproof enclosure)

Basic device

with Ex ia/ib protection

Basic device

with Ex n/

dust protection

Explosion protection as per ATEX

Without

Ex d

II 2 G Ex d II C T4/T5/T6

Ex ia/ib

II 2 G Ex ia/ib II C T6

Ex n

II 3 G Ex nA nL[nL] IIC T6
Dust

II 3 D Ex tD A22 IP66

T100°C

Mounting location

Zone 1

Zone 2/22

Permissible ambient temperature for

operation
At ≤ 10 °C (+14 °F) the display refresh

rate of the indicator is limited
(for basic devices with Ex protection

the following applies: Only T4 is per-

missible when using I

y

module.)

-30 ... +80 °C

(-22 ... +176 °F)

T4: -30 ... +80 °C

(-22 ... +176 °F)

T5: -30 ... +65 °C

(-22 ... +149 °F)

T6: -30 ... +50 °C

(-22 ... +122 °F)

T4: -20 ... +75 °C

(-4 ... +167 °F)

Electrical specifications
Input
Power supply (terminals 6/7)

Bus-supplied

Bus voltage

9 ... 32 V

9 ... 24 V

9 ... 32 V

• Bus connection with supply unit

Intrinsically safe FISCO

at "nA" and "tD":

Un = 32 V DC
at "nL":

FNICO

- Max. supply voltage U

o

17.5 V

- Max. short-circuit current I

o

380 mA

570 mA

- Max. power P

o

5.32 W

• Bus connection with barrier

intrinsically safe

at "nL"

- Max. supply voltage (Uo)

24 V

32 V

- Max. short-circuit current (Io)

250 mA

- Max. power P

o

1.2 W

Electrical specifications

Current consumption

10.5 mA ± 10 %

Additional error signal

0 mA

Effective internal inductance L

i

8 μH

8 μH (at "nL")

Effective Internal capacitance C

i

Negligible

Safety shutdown can be activated

with coding bridge (terminals 81/82;

electrically isolated from the basic

device)
• Input resistance

> 20 kΩ

• Signal status "0" (shutdown active)

0 ... 4.5 V or unused

• Signal status "1"

(shutdown not active)

13 ... 30 V

• Effective Internal capacitance C

i

Negligible

• Effective internal inductance L

i

Negligible

• For connection to power supply with

intrinsically safe

At "nA", "nL" and "tD"

- Max. supply voltage U

i

30 V

- Max. short-circuit current I

i

100 mA

- Maximum power P

i

1 W

Electrical isolation

Between basic device and the input for safety shut-

down, as well as the outputs of the option modules

The basic device and the

input to the safety shut-

down, as well as the out-

puts of the option

modules, are separate,

intrinsically safe circuits

Between basic device

and the input for safety

shutdown, as well as the

outputs of the option

modules

Test voltage

840 V DC, 1 s