Alpha Technologies GMX-915 User Manual
Page 9

9
017-932-B0-002, Rev. B
Utility Power Connection Notes
Connecting to the utility should be performed only by qualified service personnel and in compliance with local
electrical codes. Connection to utility power must be approved by the local utility before installing the power
supply.
ATTENTION:
UL and NEC require that a service disconnect switch (UL listed) be provided by the installer and be connected
between the power source and the GMX Power Supply. Connection to the power supply must include an
appropriate service entrance weather head.
ATTENTION:
In order to accommodate the high-inrush currents normally associated with the start-up of ferroresonant
transformers (400A, no-trip, first-half cycle), either a “high-magnetic” or HACR (Heating, Air Conditioning,
Refrigeration) trip breaker must be used. Do not replace these breakers with a conventional service entrance
breaker. Alpha recommends ONLY Square D breakers because of increased reliability in this powering
application. High-magnetic Square D circuit breakers and BBX option (UL Listed service entrance) are
available from Alpha Technologies.
NOTE:
GMX Line Cord Options
Alpha P/N
Line Cord, IEC 320 to NEMA 5/20P, SJT 12AWG (US)
875-25-19
Line Cord,3C, #14, SCHUKO/320 C19 RECT, 1M (EU)
875-32-10
Line Cord, 3C, #14, SCHUKO/IEC 320 C19 REPT, 2.5M (EU)
875-33-10
Line Cord,3C, #14, BS546/IEC 320 C19 RCPT, 1M (India)
875-3-10
Line Cord,3C, #14, BS1363/IEC 320 C19 RCPT, 2M (UK)
875-35-10
Line Cord,3C, CHN/IEC 320 C19 RCPT, 1M (China)
875-36-10
Line Cord, 3-conductor, 12AWG, NEMA 6-15P (US)
875-71-10
Description
Alpha P/N
Square D Part Number
240V Installation — HACR (15A)
70-22-10
QO215
120V Installation — High-magnetic (20A)
70-017-10
QO120HM
120V Installation — High-magnetic (15A)
70-013-10
QO115HM
BBX — External Service Disconnect
020-085-10
QO2-L70RB
BBX — External Service Disconnect
020-11-10
QO8-16L100RB