Utility Power Connection Notes

Connecting to the utility should be performed only by qualified service personnel and in compliance with local

electrical codes. Connection to utility power must be approved by the local utility before installing the power

supply.

ATTENTION:

UL and NEC require that a service disconnect switch (UL listed) be provided by the installer and be connected

between the power source and the GMX Power Supply. Connection to the power supply must include an

appropriate service entrance weather head.

ATTENTION:

In order to accommodate the high-inrush currents normally associated with the start-up of ferroresonant

transformers (400A, no-trip, first-half cycle), either a “high-magnetic” or HACR (Heating, Air Conditioning,

Refrigeration) trip breaker must be used. Do not replace these breakers with a conventional service entrance

breaker. Alpha recommends ONLY Square D breakers because of increased reliability in this powering

application. High-magnetic Square D circuit breakers and BBX option (UL Listed service entrance) are

available from Alpha Technologies.

NOTE:

GMX Line Cord Options

Alpha P/N

Line Cord, IEC 320 to NEMA 5/20P, SJT 12AWG (US)

875-25-19

Line Cord,3C, #14, SCHUKO/320 C19 RECT, 1M (EU)

875-32-10

Line Cord, 3C, #14, SCHUKO/IEC 320 C19 REPT, 2.5M (EU)

875-33-10

Line Cord,3C, #14, BS546/IEC 320 C19 RCPT, 1M (India)

875-3-10

Line Cord,3C, #14, BS1363/IEC 320 C19 RCPT, 2M (UK)

875-35-10

Line Cord,3C, CHN/IEC 320 C19 RCPT, 1M (China)

875-36-10

Line Cord, 3-conductor, 12AWG, NEMA 6-15P (US)

875-71-10

Description

Alpha P/N

Square D Part Number

240V Installation — HACR (15A)

70-22-10

QO215

120V Installation — High-magnetic (20A)

70-017-10

QO120HM

120V Installation — High-magnetic (15A)

70-013-10

QO115HM

BBX — External Service Disconnect

020-085-10

QO2-L70RB

BBX — External Service Disconnect

020-11-10

QO8-16L100RB