beautypg.com

2 inverter overview, Inverter overview – Alpha Technologies GMX-915 User Manual

Page 15

background image

15

017-932-B0-002, Rev. B

1.0

Introduction to the GMX Power Supply, continued

1.2 Inverter Overview

The inverter provides uninterrupted power to the ferroresonant transformer (via the batteries)

during line failures. During line operation, the inverter charges the batteries using a three-

stage (Bulk, Accept, and Float) charger.

Components:

• Smart Display: All operational functions, system testing, setup items, and alarms are

available via the Smart Display panel on the front of the GMX Power Supply (the Smart

Display is covered in detail in Section 5.2). Display functions are accessible by pressing

any of the four keys: ESCAPE, UP, DOWN, and ENTER. Backlighting is activated when

any of the four keys are pressed, and stays illuminated for one hour. There are four

levels of menu items: Normal operation, Additional Information, Setup, and Alarms. Press

ENTER to display one level lower. Press ESCAPE to display one level higher. Press

ESCAPE to toggle between the main menu and alarm menu when alarms are present.

• Battery Breaker: The battery breaker disconnects the batteries from the inverter's

DC circuit. With the battery breaker turned off, the GMX Power Supply will not transfer

to standby mode, the inverter is disabled, and the battery charger cannot charge the

batteries. If an overcurrent is detected in the DC circuitry the breaker will trip.

• Battery Input Connector (Red = Positive; Black = Negative): The batteries plug directly

into the inverter’s battery connector. The connector is color-coded and fits in one direction

only.

• Inverter Cooling Fan: The inverter is equipped with a cooling fan that operates during

standby operation, or when the inverter heatsink temperature reaches 85°C. The fan

stays on until the temperature drops below 75°C. The fan also operates any time a self-

test is in progress.

• Battery Temp Probe Connector: The Remote Temperature Sensor (RTS) plugs directly

into the temperature probe (RJ-11C type) connector. The sensor end of the RTS is routed

to the battery compartment and taped directly to the side of the center battery. The RTS

provides battery temperature measurements used to adjust the battery charge voltage.

Fig. 1-3, Inverter Overview

Status LEDs

Smart Display

Battery Input

Battery

Breaker

Battery Temperature

Probe Connector

Inverter

Cooling Fan

Terminal Block