beautypg.com

Alpha Technologies GMX-915 User Manual

Page 11

background image

11

017-932-B0-002, Rev. B

240Vac Service Entrance, GMX 225V, U.S. Domestic Models

These configurations are equipped with a 240Vac duplex receptacle to provide power to the power supply

and peripheral equipment. The receptacle, NEMA 6-15R, is protected by a single, 2-pole, common trip 15A

circuit breaker located inside the service entrance. Wiring is typical 1AWG per NEC code, and a grounding

clamp, located on the enclosure, facilitates dedicated grounding.

Utility Power Connection Notes, continued

Typical 220, 230, 20Vac 15A Service Entrance Wiring, International

To bond the box to a neutral plate, use the long green bonding screw provided (Alpha P/N 523-011-10).

NOTE:

220, 230, 240Vac Service Entrance, GMX 225V, International Models

Typical 20Vac Service Entrance Wiring, U.S. Domestic Markets

Line (Black)

Neutral Bus

LI

Grounding Point Made

to Enclosure Wall

Copper Ground Wire

#8 AWG (Minimum)

Breaker

To Utility

Neutral (White)

L2

L2

L1

Line (Black)

Neutral Bus

LI

Grounding Point Made

to Enclosure Wall

Copper Ground Wire

#8 AWG (Minimum)

Breaker

To Utility

Neutral (White)