017-932-B0-002, Rev. B

8.0

Troubleshooting, continued

8.3 Emergency Shutdown

The GMX Power Supply contains more than one live circuit. During an emergency, utility

power may be disconnected at the service entrance or main electrical panel to protect

emergency personnel. Power may still present at the output. To prevent the possibility of

injury to service or emergency personnel, always follow this procedure to safely shutdown the

power supply.

Emergency Shutdown Procedure:
STEP 1
:

Turn the battery breaker to OFF.

STEP 2:

Unplug the AC Input Line Cord from the service entrance.