017-932-B0-002, Rev. B

5. 0 Operation, continued

5.3

Smart Display Glossary, continued

Standby Time: The total amount of time the GMX Power Supply has operated in standby

mode. This does not include self-test time and thus represents the sum total number of

minutes of AC line failure since the last time this counter was reset. Use the Setup Menu to

reset Standby Time to zero.
Test Countdown: The number of days remaining before the next scheduled automatic self-

test is initiated. This variable is programmable and allows the operator to select the day that

the autotest sequence will begin. This counter has no effect if test interval is set to 0.
Test Duration: Automatic self-test duration timer. The number of minutes the GMX Power

Supply performs battery maintenance cycle test. This timer applies to initiated tests

automatically or manually.
Test Inhibit: Becomes active when programmed by the operator (or when the unit runs

in inverter mode for more than 5 minutes). The GMX Power Supply delays the start of a

scheduled self-test for seven days if the test countdown is less than seven days (See Section

5.4, Automatic Performance Test for complete details).
Test Interval: Automatic self-test control timer. The number of days between battery

maintenance cycle tests. Setting this value to zero disables automatic self-test.
Total Run Time: The amount of time (in days) the power supply has functioned in any mode

of operation. This is not a re-settable value.

Resetting factory defaults does not clear Standby Events or Standby Time.

NOTE: