017-932-B0-002, Rev. B

Utility Power Connection Notes

In most cases, the following configurations qualify for service entrance use when wiring a duplex receptacle

to a service disconnect. Other codes may also apply. Always contact your local utility to verify that the wiring

conforms to applicable codes.

120Vac 20A Service, GMX 115V, U.S. Domestic Models

These configurations are equipped with a 120Vac duplex receptacle which provides power to the power

supply and peripheral equipment. The receptacle, NEMA 5-20R, is protected by a single-pole, 20A High

Magnetic (HM) circuit breaker located inside the service entrance. Wiring is typical 12AWG per NEC code,

and a grounding clamp, located on the enclosure, facilitates dedicated grounding.

To bond the box to a neutral plate, use the long green bonding screw provided (Alpha P/N 523-011-10).

Typical 120 Vac 20A Receptacle Wiring, 5-20R

(P/N 531-006-10)

Neutral

(White)

LI

(Black)

Ground

(Green)

ATTENTION:

NOTE:

L1 Black

Typical 120Vac Service Entrance Wiring

To Utility

Neutral (White)

Neutral Bus

To Enclosure Receptacle

L1 Black

Grounding Point

(made to enclosure wall)

Copper Ground Wire

#8AWG (minimum)

Breaker