017-932-B0-002, Rev. B

If an GMX Power Supply is used in a non-standby application, this variable must be programmed to “0” to

disable the battery maintenance cycle portion of a self-test.

End of Battery Discharge (EOD): The point at which the batteries are fully discharged

(1.75V/C°, 18 cells for 36V inverter) and the power supply shuts off, preventing permanent

damage to the batteries.
Frequency Range Limit (may be used when powering with AC Generator): AC input voltage

frequency range limit. This limit establishes the acceptable input frequency range outside of

which standby operation is initiated.
Set Defaults: When programmed by the operator to YES, all the programmable data levels

(except DEVICE ADDRESS) are reset to the original factory settings.
Self-test: When programmed by the operator to YES, the GMX Power Supply will test

inverter operation.
Standby Events: GMX Power Supply standby events counter. This does not include self-test

events. Use the Setup Menu to reset Standby Events to zero.

5.0

Operation, continued

5.3 Smart Display Glossary

Battery Capacity: The capacity of the battery strings attached to this GMX Power Supply.

When batteries are not attached, the setting may be programmed to “0.” This disables

standby operations, including test mode, and disables the No Batteries Alarm. If batteries are

attached, then this setting should be programmed to the total rating of all battery strings. This

setting can be programmed to higher values to accommodate multiple battery strings (i.e., 1

battery string = 100Ah, 2 battery strings = 200Ah, 3 battery strings = 300Ah).

BULK charge is a “Constant Current” charge. Ten amps is the maximum the charger is

capable of delivering. As the charge is returned to the batteries, their voltage increases to

a specific threshold (2.27Vdc per cell). This cycle ends when the charging current into the

batteries becomes less than 0.5A.The charger then switches to ACCEPT mode. The BULK

charger mode generally returns the battery charge state to 80 percent of rated battery

capacity.
Charger Accept Voltage: Battery Accept charge voltage control in volts per cell. This

voltage, 2.40Vdc (adjustable) per cell, is temperature compensated to assure longer battery

life. It properly completes the charge cycle and is factory set for Alpha Cell batteries. If other

manufacturer’s batteries are used, consult the battery manufacturer for Accept voltage levels.
Charger Float Voltage: Battery Float charge voltage control in volts per cell. It averages

about 2.27Vdc (adjustable) per cell. It is factory set for Alpha Cell batteries. If other

manufacturer’s batteries are used, consult the battery manufacturer for Float voltage levels.
Charger Temperature Compensation: Battery charger temperature compensation control.

Programming this parameter to “0.0” will disable temperature compensation. It is factory set

for Alpha Cell batteries (5mV/cell/ºC). If other manufacturer’s batteries are used, consult the

battery manufacturer for Charger Temperature compensation ranges.
Device Address: The GMX Power Supply must have a unique address to communicate with

a system controller. The system controller uses the address as an identifier to query the GMX

Power Supply for information. Each GMX Power Supply on the same communications bus

must be identified with a value between 1 and 7.

NOTE:

The device address will not reset to 1 when factory defaults are reset.

NOTE: