Smart Display, continued

5.2.6 Detailed Menu Structure and Navigation, continued

***ACTIVE ALARMS***

(Single Step Information)

Self-test Fail

Low Batt Volts

High Batt Volts

No Batteries

Batt Temp Probe

Line Isolation

Output Failure

Output Overload

Charger Failure

Input Failure

Inv Disconnected

Inverter Temp

Config Error

ACTIVE ALARMS

(Auto-scrolling Information)

Input Voltage 20V
Battery Volts 0.5V

Output Voltage 90V

Output Current 12.2A

12 Events 65 M

Charger Mode = Float

Oper Mode = Line

ACTIVE ALARMS

(Single Step Information)

Input Voltage 20V
Battery Volts 0.5V

Output Voltage 90V

Output Current 12.2A

12 Events 65 M

Charger Mode = Float

Oper Mode = Line

Additional Information

(Single Step Information)

Battery Temp 37ºC

Charger Curr 8.2A

Input Frequency 60.1Hz

Output Watts 900W

Output VA 1060

Percent Load 80%

SETUP MENU

(Single Step Information)

Float V/C = 2.27

Accept V/C = 2.0

Temp Comp = 5.0mV

Batt Capacity = 100Ah

Self-test = ON

Test Inhibit = OFF

Test Interval = 30 D

Test Countdown = 30 D

Test Duration = 10 M

Freq Range = +/- 3Hz

Standby Time = Min

Standby Events

Set Defaults

Code Ver 1.00.0

XM2 Class Ver

Device Address 1

Total Runtime

OUTPUT OVERLOAD

(Auto-scrolling Information)

1. Output Short Ckt
2. Too Much Load
3. Chk Output Current

OUTPUT OVERLOAD

(Single Step Information)

1. Output Short Ckt
2. Too Much Load
3. Chk Output Current

LEGEND

ESCAPE

ESC

ENTER

DOWN Arrow

UP Arrow

Control

Panel

Key

Display

Symbol

Description

***ACTIVE ALARMS***

(Auto-scrolling Information)

Self-test Fail

Low Batt Volts

High Batt Volts

No Batteries

Batt Temp Probe

Line Isolation

Output Failure

Output Overload

Charger Failure

Input Failure

Inverter Temp

Config Error

ESC

SETUP MENU

(Auto-scrolling Information)

Float V/C = 2.27

Accept V/C = 2.0

Temp Comp = 5.0mV

Batt Capacity = 100Ah

Self-test = ON

Test Inhibit = OFF

Test Interval = 30 D

Test Countdown = 30 D

Test Duration = 10 M

Freq Range = +/- 3Hz

Standby Time = Min

Standby Events

Set Defaults

Code Ver 1.00.0

XM2 Class Ver

Device Address 1

Total Runtime

Additional Information

(Auto-scrolling Information)

Battery Temp 37ºC

Charger Curr 8.2A

Input Frequency 60.1Hz

Output Watts 900W

Output VA 1060

Percent Load 80%

ESC

ESC

ESC

ESC

Edit Using

ESC

ESC

ESC

ESC

ESC

ESC

Back to Setup Menu

Edit Using:

Float V/C = 2.27V

To Program Mode

To Accept New Data

to Abort

Abort

Data Accepted

To Accept

New Data

Back to Single Step Menu

Back to Auto-scroll

To Single Step

To Additional Information

To Setup Menu

Back to

Auto-scroll

To Single Step

To Additional

Information

To Additional

Information

To Single Step

Back to

Auto-scroll

To System Info

To Active Alarm List

Note: Only

Detected

Alarms will

appear in this

menu

Note: Only

Detected

Alarms will

appear in this

menu

To Single

Step

Back to

Auto-scroll

Back to

Auto-scroll

To Help

Screens for

Selected Alarm

To Single Step

Help Screens

Back to

Auto-scroll

Help Screens

To System Info

To Setup Menu