2 smart display, continued – Alpha Technologies GMX-915 User Manual
Page 43

3
017-932-B0-002, Rev. B
5.2
Smart Display, continued
5.2.6 Detailed Menu Structure and Navigation, continued
***ACTIVE ALARMS***
(Single Step Information)
Self-test Fail
Low Batt Volts
High Batt Volts
No Batteries
Batt Temp Probe
Line Isolation
Output Failure
Output Overload
Charger Failure
Input Failure
Inv Disconnected
Inverter Temp
Config Error
ACTIVE ALARMS
(Auto-scrolling Information)
Input Voltage 20V
Battery Volts 0.5V
Output Voltage 90V
Output Current 12.2A
12 Events 65 M
Charger Mode = Float
Oper Mode = Line
ACTIVE ALARMS
(Single Step Information)
Input Voltage 20V
Battery Volts 0.5V
Output Voltage 90V
Output Current 12.2A
12 Events 65 M
Charger Mode = Float
Oper Mode = Line
Additional Information
(Single Step Information)
Battery Temp 37ºC
Charger Curr 8.2A
Input Frequency 60.1Hz
Output Watts 900W
Output VA 1060
Percent Load 80%
SETUP MENU
(Single Step Information)
Float V/C = 2.27
Accept V/C = 2.0
Temp Comp = 5.0mV
Batt Capacity = 100Ah
Self-test = ON
Test Inhibit = OFF
Test Interval = 30 D
Test Countdown = 30 D
Test Duration = 10 M
Freq Range = +/- 3Hz
Standby Time = Min
Standby Events
Set Defaults
Code Ver 1.00.0
XM2 Class Ver
Device Address 1
Total Runtime
OUTPUT OVERLOAD
(Auto-scrolling Information)
1. Output Short Ckt
2. Too Much Load
3. Chk Output Current
OUTPUT OVERLOAD
(Single Step Information)
1. Output Short Ckt
2. Too Much Load
3. Chk Output Current
LEGEND
ESCAPE
ESC
ENTER
DOWN Arrow
UP Arrow
Control
Panel
Key
Display
Symbol
Description
***ACTIVE ALARMS***
(Auto-scrolling Information)
Self-test Fail
Low Batt Volts
High Batt Volts
No Batteries
Batt Temp Probe
Line Isolation
Output Failure
Output Overload
Charger Failure
Input Failure
Inverter Temp
Config Error
ESC
SETUP MENU
(Auto-scrolling Information)
Float V/C = 2.27
Accept V/C = 2.0
Temp Comp = 5.0mV
Batt Capacity = 100Ah
Self-test = ON
Test Inhibit = OFF
Test Interval = 30 D
Test Countdown = 30 D
Test Duration = 10 M
Freq Range = +/- 3Hz
Standby Time = Min
Standby Events
Set Defaults
Code Ver 1.00.0
XM2 Class Ver
Device Address 1
Total Runtime
Additional Information
(Auto-scrolling Information)
Battery Temp 37ºC
Charger Curr 8.2A
Input Frequency 60.1Hz
Output Watts 900W
Output VA 1060
Percent Load 80%
ESC
ESC
ESC
ESC
Edit Using
ESC
ESC
ESC
ESC
ESC
ESC
Back to Setup Menu
Edit Using:
Float V/C = 2.27V
To Program Mode
To Accept New Data
Abort
Data Accepted
To Accept
New Data
Back to Single Step Menu
Back to Auto-scroll
To Single Step
To Additional Information
To Setup Menu
Back to
Auto-scroll
To Single Step
To Additional
Information
To Additional
Information
To Single Step
Back to
Auto-scroll
To System Info
To Active Alarm List
Note: Only
Detected
Alarms will
appear in this
menu
Note: Only
Detected
Alarms will
appear in this
menu
To Single
Step
Back to
Auto-scroll
Back to
Auto-scroll
To Help
Screens for
Selected Alarm
To Single Step
Help Screens
Back to
Auto-scroll
Help Screens
To System Info
To Setup Menu