GMX Power Supply Maintenance, continued

6.4 Check Battery Charger Voltage

The advanced three-stage charging features of the GMX Power Supply are completely self-

monitoring. During normal power supply operations, the power supply continuously verifies

the operating condition of the battery charger. If, for any reason, the battery charger fails, a

Charger Fail alarm displays on the Smart Display. No operator voltage checks are required.

6.5 Check Battery Terminals and Connecting Wires

Check each battery terminal and connection. Verify the posts are clean and the crimped

connectors are tight. Terminal connectors should be torqued in accordance with the battery

manufacturer's recommendation. If there is an in-line fuse in the battery cable, check the fuse

holder and fuse. Verify the terminals are properly protected with an approved battery terminal

corrosion inhibitor such as NCP-2. Record date of maintenance in the maintenance log.

6.6 Check Output Voltage

Measure the AC output voltage at the GMX Power Supply Transformer Module’s V

out

±

terminals (Output test points) using a true RMS AC voltmeter. Only use a True RMS meter, as

other meters may not give a correct reading.
Output voltages should appear within ±5% of rated output at a nominal line input.
Record the voltages in the maintenance log. Output voltages can also be observed by using

the Smart Display.

Whenever the battery breaker is turned off, or the batteries are not connected, the GMX Power Supply

automatically reports a No Batteries alarm. This is normal, and is a built in safety feature. The unit does not

attempt inverter operations, either standby or test, during a No Battery alarm.

NOTE:

Setting

Low (-5%)

High (+5%)

87Vac

82.65Vac

91.35Vac

63Vac

59.85Vac

66.15Vac

6.7 Check Output Current

With the GMX Power Supply in normal operating mode observe the Smart Display Output

Current. The value of output current will be dependent on the total amount of load connected

to the power supply. Record the current in the maintenance log.