Alpha Technologies GMX-915 User Manual
Page 37

37
017-932-B0-002, Rev. B
5.0
Operation, continued
5.2
Smart Display, continued
5.2.3 Setup Menu, continued
The Setup Menu contains the following items:
Top Line (provides additional information)
• SET UP MENU
•
TO MANUAL SCROLL
•
Second Line (cycles through the following parameters):
Refer to Section 5.3, Smart Display Glossary, for descriptions of the setup menu parameters.
NOTE:
Default
Minimum
Maximum
Float V/C
2.27
2.1V/Cell
2.35V/Cell
Accept V/C
2.0
2.2V/Cell
2.5V/Cell
Temp Comp
5mV/Cell/ºC
0mV/Cell/ºC
5mV/Cell/ºC
Battery Capacity*
100Ah
0Ah
1000Ah
Self-test
Off
On
Off
Test Inhibit
N/A
7 days
7days
Test Interval
30 days
0 days
360 days
Test Countdown
0 days
0 days
365 days
Test Duration
10 minutes
5 minutes
180 minutes
Frequency Range
3Hz
1Hz
6Hz
Standby Time
0 minutes
0 minutes
65,535 minutes
Standby Events
0 events
0 events
65,535 events
Set Defaults
No
No
Yes
Code Version
1.00.0
GMX_Class Version
Device Address
1
0
7
Total Runtime
0 days
0 days
65,535 days
* 100Ah = 1 battery string, 200Ah = 2 battery strings, 300Ah = 3 battery strings
Table 5-1, Setup Menu Parameters
Battery voltage is limited to the range 2.20 V/Cell (min.) to 2.50 V/Cell (max.) regardless of temperature or
temperature compensation settings.
NOTE: