beautypg.com

8 replacing the metal oxide varistors, Replacing the metal oxide varistors, P3 p9 p8 (not shown) – Alpha Technologies GMX-915 User Manual

Page 53

background image

53

017-932-B0-002, Rev. B

6.0

GMX Power Supply Maintenance, continued

6.8 Replacing the Metal Oxide Varistors

The Power Distribution Board (PDB) uses three Metal Oxide Varistors (MOVs) for lightning

suppresson. If the MOVs fail, Alpha offers a replacement board option to bring the unit back

into service.

Tools Required:

#2 Phillips screwdriver

Wire cutters

Procedure:

1. Remove all power to unit. Turn off battery breaker and unplug battery connector. Unplug

line cord and remove all front panel connectors.

Fig. 6-1, MOV Removal

2. Remove the eight screws securing the power supply front panel. Set the screws aside in

a safe location.

3. Tip the front panel forward to gain access to the Power Distribution Board.

. Remove the damaged MOVs using your wire cutters. See Fig. 6-1.

5. Replace with the MOV replacement card option (Alpha P/N 704-804-20). Position the

card over P3, P9, and P8 and seat firmly as shown in Fig. 6.2.

6. Replace the front cover.

Before proceeding, verify all power has been removed from the power supply by

unplugging the power supply from the AC power source and disconnecting the battery

connector. Failure to do so could expose the technician to potentially lethal voltages.

WARNING!

Fig. 6-2, MOV Replacement

P3

P9

P8

(not shown)