Page 30

background image

30

017-932-B0-002, Rev. B

SETTING

LOW (-5%)

HIGH (+5%)

87Vac

82.65Vac

91.35Vac

63Vac

59.85Vac

66.15Vac

Self-test Operation

1. The GMX Power Supply should be operating correctly with no alarms present. Use the

Smart Display to verify Normal and Additional Information. Verify test duration in the

Setup Menu as needed.

2. Press and hold DOWN and ENTER simultaneously to start Self-test. The test runs for a

preset time (5 to 180 minutes, set in the Setup Menu). Self-test can also be entered by

setting Self-test to ON in the Setup Menu.

3. While in Self-test mode, use the Smart Display or a true RMS voltmeter to verify output

at the terminal block V

out

terminals. Output voltages should appear within ±5% of 87Vac

(for 90V units) and 63Vac (for 60V units), at nominal line input voltage.

5.0

Operation, continued
5.1

Start-up and Test, continued

AC Line Operation, continued

6. Use the Smart Display or a true RMS voltmeter to verify AC output (±5%) at the module’s

V

out

± terminals (AC Output test point). If a non-RMS voltmeter is used, the output

reading can vary by as much as 10% due to the “quasi” square wave output of the

ferroresonant transformer.

. To cancel a Self-test in progress, push and hold DOWN and ENTER a second time, or

change Self-test to OFF in the Setup Menu.

SETTING

LOW (-5%)

HIGH (+5%)

87Vac

82.65Vac

91.35Vac

63Vac

59.85Vac

66.15Vac

7. Use the Smart Display to verify GMX Power Supply operations. Press ENTER ( ) to

view Normal Information. Press ENTER ( ) again to view Additional Information. Press

ENTER ( ) a third time to view the Setup Menu. If desired, the No Battery alarm can be

disabled by changing Battery Capacity to “0”.

The Configuration Screen can be accessed any time by simultaneously pressing UP and ENTER ( ).

NOTE:

Disabling the No Battery alarm is only recommended for applications not using batteries.

NOTE: