17

017-932-B0-002, Rev. B

1.0

Introduction to the GMX Power Supply, continued

1.4 Optional Features

The following options can be factory installed, or upgraded in the field by the user:

Local and Remote Indicator (LRI)

The LRI (red) lamp is located on the outside of pole-mount enclosures. During normal AC

line operation, the LRI remains off. The LRI comes on only when the power supply is running

in Standby Mode. Whenever a fault is detected during self-test, the LRI flashes to indicate

that service is required. The LRI is a simple form of status monitoring that allows operators to

check the operational status of the power supply without having to climb the pole and open

the enclosure (Alpha P/N: 740-139-25).

AC Indicator (ACI)

The AC Indicator (green lamp) is located next to the LRI on the outside of pole-mount

enclosures. As long as there is voltage present at the output, the ACI remains on. As with the

LRI, it acts as a simple form of status monitoring that allows cable technicians to check the

output status of the power supply without having to climb the pole and open the enclosure.

Alpha recommends using the ACI-LL (long life LED) because it provides much longer life

than the original light bulb design. Models for 60V and 90V are available. ACIs are not

recommended for ground mount enclosures (Alpha P/N: 740-167-21).

LA-P+ 120V, 240V (Lightning Arrestor)

The LA-P+ plugs directly into the enclosure’s convenience outlet, to provide additional

protection from voltage spikes caused by lightning and other power disturbances. It

eliminates the need for hard-wired MOVs. No additional wiring is necessary (120V, Alpha

P/N: 020-098-24 or 240V, Alpha P/N: 020-098-25).

APP90S /APP9022S (Service Power Supply)

The APP90S/APP9022S is a portable, non-standby power supply that provides conditioned

AC power to the load when the main power module is out of service. An internal tap allows

the APP90S/APP9022S to be set for 90/75/60Vac applications. Using a 15A or 25A SPI

(Service Power Inserter), power can be transferred from the APP9015S/APP9022S to the

load.

Utility safety ground must meet NEC standards.

ATTENTION:

1.5 Handle Cover

The GMX Power Supply is equipped with a sliding handle cover to reduce the risk of dropping

tools or hardware into the power supply.

Closed Handle Cover

Open Handle Cover

Loosen Bolts