017-932-B0-002, Rev. B

6.0 GMX Power Supply Maintenance

Maintenance must be performed every three to six months. By establishing a routine maintenance

program, and following the guidelines contained in this manual, the GMX Power Supply will provide

years of trouble-free operation.
Care of the batteries is the first step in any power supply maintenance program. In addition to

voltage checks, visually inspect the batteries for signs of cracking, leaking, or swelling. To aid in

quick identification and tracking of voltages in the maintenance log, number the batteries inside the

enclosure using labels or masking tape, etc. Batteries are temperature sensitive and susceptible to

overcharging and undercharging. Since batteries behave differently in the winter than in the summer,

Alpha’s battery chargers automatically compensate for changes in temperature by adjusting float and

accept charge voltages.

6.1 Check Battery Open Circuit Voltage

Prior to testing, record the battery manufacturer, date code, lot number, and power supply’s

model number and serial Number.
Inspect all battery posts, verify that all connections are clean and tight. Reapply corrosion

inhibitor.
Disconnect the AlphaGuard CMT (if used) and switch the front panel battery breaker of the

GMX Power Supply Inverter to OFF. Disconnect the battery connector from the inverter and

measure the individual voltage across each battery. The difference between any battery in the

string should not be greater than 0.3Vdc. Defective or marginal batteries should be replaced

with an identical type of battery. Record the unloaded battery voltages in the maintenance

log.

6.2 System Information

Observe and record the following system information from the Normal Operation and

Additional Information menus in the maintenance log. See Section 6.9.

CAUTION!

The GMX Power Supply must be serviced by qualified personnel.
Use heavy gloves when handling a GMX Power Supply that has just been taken out of service. The

ferroresonant transformer generates heat that may cause burns if handled with bare hands.

Alpha Technologies is not responsible for battery damage due to improper charger voltage settings.

Consult the battery manufacturer for correct charger voltage requirements.

When removing batteries, ALWAYS switch the battery breaker off before unplugging the battery connector.
• Always wear safety glasses when working with batteries.

Operation Normal

Input Voltage

Output Voltage
Output Current

Standby Events

Battery Voltage

Charger Mode

Total Standby Time

Operation Mode

Addtional Information

Battery Temperature

Output Voltage

Input Frequency

Output Watts

Output VA

Percent Load