5.2

Smart Display, continued

5.2.1 Operation Normal

If no alarms are present, the GMX Power Supply operates in the Operation Normal

mode. This mode allows the operator to view the primary operating parameters of the

power supply. In this mode, the display will auto scroll through the available menu

items at two-second intervals. In the Normal Operation mode, the displayed items are

all “metered” items, and are for informational purposes only (not programmable) with

respect to the operational status of the power supply.

The Normal Operation menu contains the following items:

Top Line (provides additional instructions):

• OPERATION NORMAL

TO MANUAL SCROLL

FOR ADDIT’L INFO

Second Line (cycles through the following parameters):

• INPUT VOLTAGE xxxV

• BATT VOLTS xx.xV

• OUTPUT VOLTAGE xxV

• OUTPUT CURRENT xx.xA

xx EVENTS xxx MIN

• CHARGER MODE = float

• OPER MODE = line

Fig. 5-3, Normal Operation Display

(Examples are given for values in the display)

OPERATION NORMAL

INPUT VOLTAGE

240V

BATTERY VOLTS

40.5V

OUTPUT VOLTAGE

87V

OUTPUT CURRENT

12.2A

12 EVENTS

65 MIN

CHARGER MODE =

FLOAT

OPER MODE =

LINE

Lower case italicized items indicate variables that change according to the operating mode, setup, or

measured values. These items will appear as normal UPPER CASE text in the actual display (see below).