1 operation normal – Alpha Technologies GMX-915 User Manual
Page 34

3
017-932-B0-002, Rev. B
5.0
Operation, continued
5.2
Smart Display, continued
5.2.1 Operation Normal
If no alarms are present, the GMX Power Supply operates in the Operation Normal
mode. This mode allows the operator to view the primary operating parameters of the
power supply. In this mode, the display will auto scroll through the available menu
items at two-second intervals. In the Normal Operation mode, the displayed items are
all “metered” items, and are for informational purposes only (not programmable) with
respect to the operational status of the power supply.
The Normal Operation menu contains the following items:
Top Line (provides additional instructions):
• OPERATION NORMAL
•
TO MANUAL SCROLL
•
FOR ADDIT’L INFO
Second Line (cycles through the following parameters):
• INPUT VOLTAGE xxxV
• BATT VOLTS xx.xV
• OUTPUT VOLTAGE xxV
• OUTPUT CURRENT xx.xA
• xx EVENTS xxx MIN
• CHARGER MODE = float
• OPER MODE = line
Fig. 5-3, Normal Operation Display
(Examples are given for values in the display)
OPERATION NORMAL
INPUT VOLTAGE
240V
BATTERY VOLTS
40.5V
OUTPUT VOLTAGE
87V
OUTPUT CURRENT
12.2A
12 EVENTS
65 MIN
CHARGER MODE =
FLOAT
OPER MODE =
LINE
Lower case italicized items indicate variables that change according to the operating mode, setup, or
measured values. These items will appear as normal UPPER CASE text in the actual display (see below).
NOTE: