Clearing alarms – Franklin Fueling Systems LS500 Auto Learn Line Leak Detection Installation & Users Guide User Manual
Page 22

22
Test Result Alarms
Test Result
Condition
Possible Cause
Resolution
Pass
Line is tight
Fail
Actual Leak
Line pressure variations are outside
threshold
Check for leaks, force leak test
to verify
Temperature Instability
Temperature fluctuations cause
pressure variances
Check for leaks, force leak test
to verify
Inadequate learning
Line not properly bled to zero during
learning
Re-learn the line, follow
procedures
Air was not bled out of the line prior
to learning
Purge the line, re-learn
Air in line
Line left open or air elimination loop
failing
Purge the line
Abort (no
indication)
Dispensing
A hook signal was detected, this
resets the testing
Allow test cycle to complete
before dispensing
Line disabled
Either manually, or by another
application shut the STP down
Check other alarms, find source
of interruption
Manual test started
User forced a line leak test
Cycle resets after manual test
completes
STP Shutdown 2 consecutive 3 GPH test
failures
Possible gross leak
Investigate, then Force a
Manual Gross Test
1-2 consecutive 0.2 GPH
test fails (depending on
programming)
Possible 0.2 GPH leak
Investigate, then Force a
Manual Monthly Test
1-3 consecutive 0.1 GPH
test fails (depending on
programming)
Possible 0.1 GPH leak
Investigate, then Force a
Manual Annual Test
3 consecutive catch pressure
tests that over 50 psi
High line pressure
Investigate, adjust or replace
check valve or functional
element
Catch pressure test failure
Pressure was less that 12 psi after
programmed delay when STP
turned off
Investigate, force a manual test
and observe pressure
Pressure up test failure
Pressure was less that 12 psi after
programmed delay when STP
turned on
Investigate, force a manual test
and observe pressure
Clearing Alarms
Clearing a console of alarms is important because, depending on how the T5 Series FMS console has been set up,
alarms can: disable channels, start an annunciator, or stop a line test under way.
Administrator privileges will be necessary to clear line alarms on the T5 Series FMS console. For instructions on how to
obtain an Administrator access level, please refer to the T5 Series FMS Programming Guide (p/n 000-2142) or the TS-
550evo FMS Programming Guide (p/n 000-2173).
1. Identify the alarm on the FMS Alarms screen.
2. Diagnose the condition using information found in the Alarms chapter of this guide.
3. Follow the troubleshooting steps in the previous section of this chapter to correct the issues indicated by the alarms.
4. Navigate to the Line Control screen.
5. Select
Reset Alarms on the Control screen.
6. Select
Enable/Disable on the Control screen if you were not given the choice to enable the line when the alarms were
reset.
If the condition still exists, the alarm can take up to several hours to reappear after the line is enabled.