LS-500 Alarms and Warnings

Alarms During the Learn Process

Alarm

Symptom

Possible Cause

Resolution

Failed to pressure up STP is not turning on

Verify that the 4-20 transducer is 

a relay / TPI input

Check the programming

Is the pump controller powered 

on?

Check the controller

If controlled by a relay, is the 

common of the relay wired to 110 

Volts?

Test the voltage on the relay 

common

Is another STP turning on?

Check the other STPs

STP is turning on, but 

the LS500 doesn’t see 

the pressure change

Is the 4-20 transducer in alarm?

Check alarms

Is the wrong transducer 

mapped?

Check programming

Is the clamp valve down?

Look at the pressure gauge on 

the needle valve kit for operating 

pressure

Line is not 

configured

Program mapping error

Verify programming

Program error 

detected

Console software error

Reboot console

Air in line

Console has sensed line 

pressure variations

Investigate, then Purge Line Starting 

at the Furthest Dispenser

Not learned

Learn Line (FMS > Control 

> Lines > Learn) follow learn 

procedures

Follow learn procedures

Insufficient volume

Line is too small

Leak generator not correct

Air in the line

Check line size

Review leak generator set-up

Purge air from the line

Alarms During Operation

Alarm

Symptom

Possible Cause

Resolution

Failed to pressure 

up

Pressure was less 

that 12 psi after 

programmed delay 

when STP turned on

Clogged STP intake

Investigate, force a manual test 

and observe pressure

STP is not turning on

Verify that the transducer is 

programmed as an input for the 

relay / TPI.

Check the programming

Is the pump controller powered 

on

Check the controller

If controlled by a relay, is the 

common of the relay wired to 

110 V

Test the voltage on the relay 

common

Is another STP turning on?

Check the other STPs

STP is turning on, but 

the LS500 doesn’t see 

the pressure change

Is the 4-20 transducer in alarm? Check alarms

Is the wrong transducer mapped Check programming