beautypg.com

Applications, Standard sensors, Britesensors – Franklin Fueling Systems T5 Series Fuel Management System Operators Guide User Manual

Page 8: Modules

background image

4

Applications

Applications are programs designed to function as a platform for specific Inputs/Outputs. There are two different applica-

tions available to the T5 series consoles:
System – This application is standard on all systems and monitors the console’s operational status and manages software 

options and upgrades. All preferences and configuration settings are controlled by this application (e.g., display 

options, clock and calendar). The system application is standard on every console.

Fuel Management System (FMS) –  The Fuel Management System application provides inventory management and leak 

detection for tanks, lines and sensors as well as tank, line and sensor control.  This 

application also allows users to print reports, tank tests and line tests.

A broad range of liquid products can be leak-tested and inventory-monitored using Magnetostrictive LL2 probes. These 

probes come in a variety of lengths and typically contain two floats for indicating both product and water levels inside the 

of tank. Programmable limits can be set to indicate high and low conditions.

Containment sumps, interstitial spaces, monitoring wells and other areas can be monitored for water and hydrocarbon 

intrusion using a wide range of optional Standard and BriteSensors. These sensors come in 2-wire (non-discriminating) 

and 3-wire (typically discriminating) versions. These models are listed below and can be used in any combination 

depending on site specifications.

Standard Sensors

Standard sensors do not discriminate between liquid and hydrocarbons and are typically 2-wire sensors.
TSP-EIS – Electro-optic Interstitial Sensors (3-wire, infrared, liquid sensor)
TSP-HLS – High product Level Sensor (2-wire, float switch, liquid level sensor)
TSP-ULS – Universal Liquid Sensor (2-wire, float switch, liquid level sensor)

TSP-UHS – Universal Hydrostatic Sensor (2-wire, float switch, liquid sensor)   

BriteSensors™

BriteSensors™ are 3-wire, discriminating sensors (many of which may generate multiple alarms).
TSP-DIS – Discriminating Interstitial Sensor (infrared and conductivity, liquid and vapor sensor)
TSP-HIS – Hydrostatic Interstitial Sensor (float switches, liquid level sensor)
TSP-DDS – Discriminating Dispenser sump Sensor (conductivity strip and floats, liquid and vapor sensor)
TSP-DTS – Discriminating Turbine sump Sensor (conductivity strip and floats, liquid and vapor sensor)
TSP-MWS – Discriminating ground water Monitoring Well Sensor (float and conductivity strip, liquid and vapor sensor)
TSP-DVS – Discriminating Vapor well Sensor (vapor sensor)

TSP-DMS – Discriminating Magnetostrictive Sensor

Modules

A modular bus consists of modules connected by a bus backplane. Some modules are standard in all units, while the type 

and number of other modules are dependent on the site configuration and options purchased. Most systems have empty 

slots available for future expansion. TS-5 (TS-608) consoles are not compatible with the TS-EXPC expansion console.

Standard Modules

Controller Module – Contains the primary controller and software applications as well as the user interface and printer 

controls. The module contains the Ethernet port, USB port (for external printer only), COMM port 1, 

audible horn and an optional internal modem card.

Power Supply Module – Contains a self-switching (110 & 220 VAC) input and provides power to the rest of the system. I/O 

ports include two output relays, two backup generator inputs, a Turbine Pump Interface (TPI) RS-

485 connection and the COMM 2 communications port. An optional Dispenser Interface Module 

(TS-DIMIB) or Echelon Communications Module (TS-LON) can also be added. The Power Supply 

Module also has a bus expansion port that can connect a T5 series console to a TS-EXPC 

Expansion Console.