beautypg.com

Franklin Fueling Systems T5 Series Fuel Management System Operators Guide User Manual

Page 35

background image

31

FMS

Line/Manifold Alarms

Displayed Alarm

Description

Recommended Actions

Reference Source

Dispenser Test

Failed

Line pressure must be above 12 psi 

when the pump is on; and above 7.5 psi 

while dispensing product.

Details of this test are summarized in LS500

Installation/User Guide (p/n 000-2145); see 

this guide for troubleshooting.

Applicable Equipment 

Guide*

Extended Hook

Signal

A hook signal has been active for more 

than four hours.

Details of this test are summarized in LS500

Installation/User Guide (p/n 000-2145); see 

this guide for troubleshooting.

Applicable Equipment 

Guide*

Failed to Catch

Pressure

Line pressure has dropped below 12 psi 

when the pump turned off.

Details of this test are summarized in LS500

Installation/User Guide (p/n 000-2145); see 

this guide for troubleshooting.

Applicable Equipment 

Guide*

Failed to

Pressure Up

Line pressure remained below 12 psi 

when the pump turned on.

Details of this test are summarized in LS500

Installation/User Guide (p/n 000-2145); see 

this guide for troubleshooting.

Applicable Equipment 

Guide*

Gross Leak

Detected

The product line listed with the alarm 

has failed a Gross Leak Test. 

Details of this test are summarized in LS500

Installation/User Guide (p/n 000-2145); see 

this guide for troubleshooting.

Applicable Equipment 

Guide*

Monthly Leak

Test Failed

The product line listed with the alarm 

has failed a Monthly Leak Test. 

Details of this test are summarized in LS500

Installation/User Guide (p/n 000-2145); see 

this guide for troubleshooting.

Applicable Equipment 

Guide*

Annual Leak Test

Failed

The product line listed with the alarm 

has failed a Precision Leak Test. 

Details of this test are summarized in LS500

Installation/User Guide (p/n 000-2145); see 

this guide for troubleshooting.

Applicable Equipment 

Guide*

High Pump

Pressure

Line pressure has exceeded 50 psi. 

Details of this test are summarized in LS500

Installation/User Guide (p/n 000-2145); see 

this guide for troubleshooting.

Applicable Equipment 

Guide*

Line is Not

Configured

The line listed with the alarm is not 

configured in ‘Lines’ programming, or 

the line is not properly mapped.

Programming details are summarized in 

LS500 Installation/User Guide (p/n 000-

2145); see this guide for troubleshooting.

Lines Setup in

Programming Manual / 

Applicable Equipment 

Guide*

Line Disabled

The input channel for the 4-20mA 

module connected to the line listed with 

the alarm is not configured.

Verify programming of the 4-20mA Module 

connected to the line listed with the alarm.

Module Setup in

Programming Manual / 

Applicable Equipment 

Guide*

Not Enabled

The product line listed with the alarm is 

not enabled in the programming.

Programming details are summarized in 

LS500 Installation/User Guide (p/n 000-

2145); see this guide for troubleshooting.

Applicable Equipment 

Guide*

Not Learned

The product line listed with the alarm 

has not been learned.

Programming details are summarized in 

LS500 Installation/User Guide (p/n 000-

2145); see this guide for troubleshooting.

Applicable Equipment 

Guide*

Pressure

Transducer

Failed

This alarm indicates a communication 

error between the console and the 

pressure transducer listed with the 

alarm.

Verify the wiring and operation of the 

transducer connected to the line listed with 

the alarm.

Applicable Equipment 

Guide*

Program Error

Detected

Firmware failed to function properly.

Upload the current firmware release.

Applicable Bulletins*

Pump Request

Ignored

The signal sent by the 4-20mA channel 

did not receive confirmation to turn on 

the pump listed with the alarm.

Verify 4-20mA and Relay Module 

programming.

Module Setup in

Programming Manual / 

Applicable Equipment 

Guide*

Sudden Pressure

Loss

Line pressure has dropped from 

above 12 psi to below 5 psi within five 

seconds.

Details of this test are summarized in LS500

Installation/User Guide (p/n 000-2145); see 

this guide for troubleshooting.

Applicable Equipment 

Guide*

* Bulletins and the T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on 
Franklin Fueling’s web site - http://www.franklinfueling.com/service/.   Select Technical Documentation / Fuel Management System