Franklin Fueling Systems T5 Series Fuel Management System Operators Guide User Manual

Page 33

background image

29

FMS

Tank/Manifold Alarms

Displayed Alarm

Description

Recommended Actions

Reference Source

Correction Table

Error

Correction points for the special 

tank listed with the alarm were not 

entered or were entered incorrectly.

Verify that the correction table points for the tank 

listed with the alarm are entered sequentially in 

‘Special Tanks’ Programming.

Special Tanks Setup in 

Programming Manual 

/ Manufacturers’ Tank 

Chart*

Manifold Gross

Leak Detected

The manifold listed with the alarm 

has failed a Gross Leak Test. 

Review manifold leak test history and 

programming. It may be necessary to manually 

start a Gross Leak Test to keep the manifold in 

compliance.

Tank Leak Tests -    

Type and Frequency

Manifold Leak

Detected

The manifold listed with the alarm 

has failed a Monthly Leak Test. 

Review manifold leak test history and 

programming. It may be necessary to manually 

start a Monthly Leak Test to keep the manifold 

in compliance.

Tank Leak Tests -    

Type and Frequency

Manifold SCALD

Leak Detected

The manifold listed with the alarm 

has failed a SCALD Leak Test. 

Review manifold leak test history and 

programming. It may be necessary to manually 

start a SCALD Leak Test to keep the manifold in 

compliance.

Tank Leak Tests -    

Type and Frequency

Manifold Theft

Detected

Product level in the manifold listed 

with the alarm has dropped below 

the programmed Theft Limit.

Verify that the programmed Theft limit is correct. 

Verify that the values of product loss on the 

console correspond with actual product loss in 

the tank.

Manifolds Setup in

Programming Manual

No Data Available

SCALD software has not observed 

enough ‘quiet time’ to complete one 

or more test intervals.

Allow enough time for SCALD to complete a 

test.

Tank Leak Tests -    

Type and Frequency

Tank Gross Leak

Detected

The manifold listed with the alarm 

has failed a Gross Leak Test. 

Review manifold leak test history and 

programming. It may be necessary to manually 

start a Gross Leak Test to keep the tank in 

compliance.

Tank Leak Tests -    

Type and Frequency

Tank Leak

Detected

The tank listed with the alarm has 

failed a Monthly Leak Test. 

Review tank leak test history and programming. 

It may be necessary to manually start a Monthly 

Leak Test to keep the tank in compliance.

Tank Leak Tests -    

Type and Frequency

Tank SCALD Leak

Detected

The tank listed with the alarm has 

failed a SCALD Leak Test. 

Review tank leak test history and programming.  Tank Leak Tests -    

Type and Frequency

Tank Theft

Detected

Product level in the tank listed with 

the alarm has dropped below the 

programmed Theft Limit.

Verify that the programmed Theft Limit is 

correct. Verify that the values of product loss on 

the console correspond with actual product loss 

in the tank.

Tanks Setup in

Programming Manual

* Bulletins and the T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on 

Franklin Fueling’s web site - http://www.franklinfueling.com/service/.   Select Technical Documentation / Fuel Management System

*  If the tank is not listed as a standard tank in Appendix A: Standard Tanks Table (in the T5 Series Programming Manual (p/n 000-

2142), use the tank chart from the manufacturer to create a custom correction table.