32

FMS

Sensor Alarms

Displayed Alarm

Description

Recommended Actions

Reference Source

SN2 Fuse Blown

The fuse on the channel of the 2-Wire 

Sensor Module listed with the alarm is 

blown.

Replace the 2-Wire Sensor Module* or 

use another channel on the module for 

that sensor.

Applicable Service 

Bulletins* / Sensors Setup in 

Programming Manual

SN2 Sensor On

The 2-Wire Sensor listed with the 

alarm is in alarm position.

Check wiring, sensor operation and 

location conditions.

Applicable Equipment 

Guides

SN3 Dry Well

The Monitoring Well Sensor listed with 

the alarm is not sensing water in the 

monitoring well.

Verify that there is no water in the 

monitoring well. This condition may be 

normal if no ground water exists.

Applicable Equipment 

Guides

SN3 Fuse Blown

The fuse on the channel of the 3-Wire 

Sensor Module listed with the alarm is 

blown.

Replace the 2-Wire Sensor Module* or 

use another channel on the module for 

that sensor.

Applicable Service 

Bulletins* / Sensors Setup in 

Programming Manual

SN3 Sensor On

The 3-Wire Sensor listed with the 

alarm is in alarm position.

Check wiring, sensor operation and 

location conditions.

Applicable Equipment 

Guides

SN3 Sync Error

A communications error has occurred 

between the console and the 3-Wire 

Sensor listed with the alarm.

Check wiring, sensor operation and 

location conditions. Attempt to re-

configure sensors with the ‘Configure’ 

button in 

Sensors > Control.

Sensors Setup in 

Programming Manual / 

Applicable Equipment 

Guides

SN3 No Signal

A communications error has occurred 

between the console and the 3-Wire 

Sensor listed with the alarm.

Check wiring, sensor operation and 

location conditions. Attempt to re-

configure sensors with the ‘Configure’ 

button in 

Sensors > Control.

Sensors Setup in

Programming Manual / 

Applicable Equipment 

Guides

SN3 ID Error

The 3-Wire Sensor listed with the alarm 

has been programmed incorrectly.

Verify that the 3-Wire Sensor is 

programmed to match the type of 

sensor.

Sensors Setup in the 

Programming Manual / 

Applicable Equipment 

Guides

SN3 Data Error

A communications error has occurred 

between the console and the 3-Wire 

Sensor listed with the alarm.

Check wiring, sensor operation and 

location conditions.

Applicable Equipment 

Guides

SN3 Pwr Short

The power wires of the 3-Wire Sensor 

listed with the alarm have shorted.

Check wiring, sensor operation and 

location conditions.

Applicable Equipment 

Guides

SN3 High Brine

The 3-Wire Sensor listed with the alarm 

is indicating a High Brine solution level 

near the sensor.

Check wiring, sensor operation and 

location conditions.

Applicable Equipment 

Guides

SN3 Low Brine

The 3-Wire Sensor listed with the 

alarm is indicating that a Low Brine 

solution near the sensor.

Check wiring, sensor operation and 

location conditions.

Applicable Equipment 

Guides

SN3 Product

The 3-Wire Sensor listed with the alarm 

is indicating that product is present 

near the sensor.

Check wiring, sensor operation and 

location conditions.

Applicable Equipment 

Guides

SN3 Sump Full

The 3-Wire Sensor listed with the 

alarm is indicating that the sump near 

the sensor is full of a liquid.

Check wiring, sensor operation and 

location conditions.

Applicable Equipment 

Guides

SN3 Vapor

The 3-Wire Sensor listed with the 

alarm is indicating that vapor is present 

near the sensor.

Check wiring, sensor operation and 

location conditions.

Applicable Equipment 

Guides

SN3 Water

The 3-Wire Sensor listed with the 

alarm is indicating that water is present 

near the sensor.

Check wiring, sensor operation and 

location conditions.

Applicable Equipment 

Guides

* Bulletins and the T5 Series Installation Guide (p/n 000-2150) and the T5 Series Programming Manual (000-2142) can be found on 

Franklin Fueling’s web site - http://www.franklinfueling.com/service/.   Select Technical Documentation / Fuel Management System 

*  If the tank is not listed as a standard tank in Appendix A: Standard Tanks Table (in the T5 Series Programming Manual (p/n 000-

2142), use the tank chart from the manufacturer to create a custom correction table.

 Only use the product manufacturer’s specifications sheet to accurately set volume correction parameters.
* Fuses on Sensor Modules are NOT field replaceable; the module must be replaced.