Specifications, Ac input module, 20ma analog input module – Franklin Fueling Systems T5 Series Fuel Management System Installation Guide User Manual
Page 30: Probe module, Relay module, Console, Wire sensor module, Low voltage input/output module, 10 amp relay module

©2012 FFS 000-2150 Rev. K
Specifications
The T5 series console must be mounted in a location where explosive or flammable vapors are not
present, otherwise an explosion hazard will be created which can result in severe injury, death,
serious property damage and/or environmental contamination.
AC Input Module
Number of Channels: 12 optically isolated
Input Voltage Rating: 110 – 240 VAC
Input Current Rating: 7 mA
4-20mA Analog Input Module
Number of Channels: 8
Safety Rating:
Class I, Division 1, Group D, [Ex ia] IIA
Entity Parameters
Uo = 26.25 V
Io = 98.2 mA
Co = 1.25 uF
Lo = 14.7 mH
Po = 0.64 W
Probe Module
Number of Channels: 12 (8 in the TS-608)
Safety Rating:
Class I, Division 1, Group D, [Ex ia] IIA
Entity Parameters
Uo = 28.35 V
Io = 157.5 mA
Co = 1.04 uF
Lo = 1.4 mH
Po = 1.1 W
Relay Module
Number of Channels:
8 Form C
Contact Rating:
2A @ 250V
2A @ 30 VDC
Warning
Console
Line Voltage:
90-250 V~
Frequency & Power: 50/60 Hz, 150 W maximum
Storage Temp.:
-20° to 60° C (-4° to 140° F)
Operating Temp.:
0° to 40° C (32° to 104° F)
Operating Humidity: 0 to 95%, non-condensing
Cleaning:
Cloth
or sponge slightly dampened in mild
detergent
Splash Resistance: Not to be exposed to direct spray, splash
or drips
Location:
Indoors in an office or in a non-hazardous
pollution degree 2 environment per
IEC60664
2-Wire Sensor Module
Number of Channels: 12
Safety Rating:
Class I, Division 1, Group D, [Ex ia] IIA
Entity Parameters
Uo = 6.51 V
Io = 2.04 mA
Co = 500 uF
Lo = 100 mH
Po = 3.3 mW
3-Wire Sensor Module
Number of Channels: 8
Safety Rating:
Class I, Division 1, Group D, [Ex ia] IIA
Entity Parameters
Uo = 7.71 V
Io = 573 mA
Co = 500 uF
Lo = 433 uH
Po = 932 mW
Low Voltage Input/Output Module
Number of Channels: 8 optically isolated inputs
4 analog outputs
Input Voltage Rating: 3 - 240 Volts AC or DC (AC is rms value)
Input Current Rating: 2 mA
10 Amp Relay Module
Number of Channels:
6 Form C
Contact Rating:
10A @ 250V
or ½ hp @ 240 VAC
¼ hp @ 120 VAC