Appendix 1: Probe Module (PRB)

The Probe Module (PRB) gathers data from probes and presents 

that information to the Controller Module (CM) for use in inventory 

reconciliation and reports. Each PRB can accomodate 12 probes 

and the system as a whole can accept a total of 36 probes (3 

modules with 12 inputs each) if space allows. Besides working 

with LL2 mag probes, the PRB also works with vapor flow meters 

to perform VRM functions.

Note:  There are 8 inputs in the TS-608’s Probe Module.
Note: All components located in the hazardous area must be Third Party Certified and have appropriate Entity 

Parameters (see Control Drawing 000-1722 in the back of this manual for further information).

Probe Module Specifications

Number of Channels: 12
Safety Rating:

Class I, Division 1, Group D, [Ex ia]  IIA

Entity Parameters

  Uo = 28.35 V

  Io = 157.5 mA

  Co = 1.04 uF
  Lo = 1.4 mH
  Po = 1.1 W

Figure 1-2 – PRB Connections

Probe

Module

RUN

ERR

9

8

7

–Blk

+Red

–Blk

+Red

–Blk

+Red

12

11

10

–Blk

+Red

–Blk

+Red

–Blk

+Red

3

2

1

–Blk

+Red

–Blk

+Red

–Blk

+Red

6

5

4

–Blk

+Red

–Blk

+Red

–Blk

+Red

Vapor Flow Meter

Probe

SHLD

- (BLK)

+ (RED)

SHLD

- (BLK)

+ (RED)

Non-Hazardous

Location

Hazardous Location

Class I, Division 1, Group

D, Group IIA, Zone 0

Probe

Module

TS-608

RUN

ERR

3

2

1

–BLK/

SHLD
+Red

6

5

4

8

7

–BLK/

SHLD
+Red

–BLK/

SHLD
+Red

–BLK/

SHLD
+Red
–BLK/

SHLD
+Red

–BLK/

SHLD
+Red

–BLK/

SHLD
+Red

–BLK/

SHLD
+Red

Figure 1-1 – TS-608

PRB Connections

Class I, Division 1, Group D