beautypg.com

Appendix 3: 3-wire sensor module (3wsns), Figure 3-1 – 3-wire sensors connections – Franklin Fueling Systems T5 Series Fuel Management System Installation Guide User Manual

Page 26

background image

26

Appendix 3: 3-Wire Sensor Module (3WSNS)

The 3-Wire Sensor Module (3WSNS) is designed to accept 8 

sensor inputs per module, and the system as a whole can accept 

a total of 24 sensors (3 modules with 8 inputs each). The 3WSNS 

can support standard sensors and 

BriteSensors

®

. 

BriteSensors 

are powered sensors that digitally communicate the sensor–type 

and alarm status of the sensor to the console. Most BriteSensors 

can discriminate between water and hydrocarbon products and 

produce different alarm codes for each.

 Refer to the diagram 

below to identify the types of sensors that should be used with this 

module.

Important: Brite Sensors are not approved for use in European Union markets where ATEX approved devices are

required.

Most of the Brite Sensors shown in this table are part of the UL & C-UL System Listing.

Model

Description

TSP-EIS

Electro-optical Interstitial liquid – Standard sensor

TSP-ULS

Universal Liquid – Standard sensor

TSP-HLS-15

High product Level, 15" – Standard sensor

TSP-HLS-30

High product Level, 30" – Standard sensor

TSP-HIS

Hydrostatic Interstitial reservoir – BriteSensor

TSP-HIS-XL*

Hydrostatic Interstitial reservoir, extra long – BriteSensor

TSP-DIS

Discriminating Interstitial liquid – BriteSensor

TSP-DDS

Discriminating Dispenser Sump – BriteSensor

TSP-DTS

Discriminating Turbine Sump – BriteSensor

TSP-DVS*

Discriminating Vapor – BriteSensor

TSP-MWS

Discriminating Monitoring Well – BriteSensor

* TSP-HIS-XL and TSP-DVS sensors are not covered by UL and cUL approval.

Note: Alternate sensors may be provided. All components located in the hazardous area must be Third Party Certified 

and have appropriate Entity Parameters (see Control Drawing 000-1722 in the back of this manual for further 

information).

3-Wire Sensor Module

Number of Channels: 8
Safety Rating:

Class I, Division 1, Group D, [Ex ia]  IIA

Entity Parameters

  Uo = 7.71 V

  Io = 573 mA

  Co = 500 uF

  Lo = 433 uH

  Po = 932 mW

3-Wire Sensor

Module

RUN

ERR

4

–Blk
Wht
+Red

3

–Blk
Wht
+Red

2

–Blk
Wht
+Red

1

–Blk
Wht
+Red

8

–Blk
Wht
+Red

7

–Blk
Wht
+Red

6

–Blk
Wht
+Red

5

–Blk
Wht
+Red

- (BLK)

+ (RED)

(WHT)

TSP-DTS

(Discriminating Turbine Sump)

- (BLK)

TSP-ULS

(Universal Liquid Sensor)

(WHT)

TSP-EIS

(Electro-optical Interstitial sensor)

- (BLK)

+ (RED)

(WHT)

Figure 3-1 – 3-Wire Sensors Connections