Appendix d: ac input module (aci), Dispenser hook signals, Figure d-1 – dispenser hook signal – Franklin Fueling Systems T5 Series Fuel Management System Installation Guide User Manual
Page 19: Ac input module specifications
19
Appendix D: AC Input Module (ACI)
The ACI is a non-intrinsically safe module that has 12 identical optically
isolated AC input channels that can be used for dispenser hook isolation, vapor
processor input, or as generic AC inputs. The T5 series consoles can handle a
total of 36 AC inputs or up to three AC Input Modules in one system.
Dispenser Hook Signals
The T5 Series system requires that the dispenser hook signal from every dispenser on site be wired into the console’s AC
Input Module. When making the connection for the hook signals to the AC Input Module, refer to the following diagram
and use these guidelines:
• If there are two hooks per dispenser: wire the two hooks from Dispenser 1 to AC input channels 1 & 2, the hooks from
Dispenser 2 to AC channels 3 & 4, etc..
• If there are three hooks per dispenser, then wire the three hooks of Dispenser 1 to the AC input channels 1, 2, 3 and so on.
Figure D-1 – Dispenser Hook Signal
AC Input
Module
RUN
ERR
Chan
3
Chan
2
Chan
1
Chan
6
Chan
5
Chan
4
Chan
12
Chan
11
Chan
10
Chan
9
Chan
8
Chan
7
Incoming Dispenser
Hook Signal
Line
Neutral
Line
Neutral
Line
Neutral
Vapor Processor
(optional)
Generic Device
(optional)
AC Input Module Specifications
Number of Channels:
12 optically isolated
Input Voltage Rating:
110 – 240 VAC
Input Current:
7 mA RMS