beautypg.com

Appendix d: ac input module (aci), Dispenser hook signals, Figure d-1 – dispenser hook signal – Franklin Fueling Systems T5 Series Fuel Management System Installation Guide User Manual

Page 19: Ac input module specifications

background image

19

Appendix D: AC Input Module (ACI)

The ACI is a non-intrinsically safe module that has 12 identical optically 

isolated AC input channels that can be used for dispenser hook isolation, vapor 

processor input, or as generic AC inputs.  The T5 series consoles can handle a 

total of 36 AC inputs or up to three AC Input Modules in one system.

Dispenser Hook Signals

The T5 Series system requires that the dispenser hook signal from every dispenser on site be wired into the console’s AC 

Input Module. When making the connection for the hook signals to the AC Input Module, refer to the following diagram 

and use these guidelines:
 • If there are two hooks per dispenser: wire the two hooks from Dispenser 1 to AC input channels 1 & 2, the hooks from 

Dispenser 2 to AC channels 3 & 4, etc..

 • If there are three hooks per dispenser, then wire the three hooks of Dispenser 1 to the AC input channels 1, 2, 3 and so on.

Figure D-1 – Dispenser Hook Signal

AC Input

Module

RUN

ERR

Chan

3

Chan

2

Chan

1

Chan

6

Chan

5

Chan

4

Chan

12

Chan

11

Chan

10

Chan

9

Chan

8

Chan

7

Incoming Dispenser

Hook Signal

Line
Neutral

Line

Neutral

Line

Neutral

Vapor Processor

(optional)

Generic Device

(optional)

AC Input Module Specifications

Number of Channels:

12 optically isolated

Input Voltage Rating:

110 – 240 VAC

Input Current:

7 mA RMS