Figure g-1 – exp analog input module connections – Franklin Fueling Systems T5 Series Fuel Management System Installation Guide User Manual

Page 22

background image

22

4-20mA EXP

Analog Input

Module

RUN

ERR

+

+

+

+

+

+

+

+

- (BLK)

+ (RED)

LSU500E

Hazardous Location

Non-Hazardous

Location

Explosion-Proof Conduit

- (BLK)

+ (RED)

4-20mA

Sensor

Figure G-1 – EXP Analog Input Module Connections

Appendix G: 4-20mA EXP Analog Input Module (420EXP)

The 420EXP has 8 identical channels for loop powered non-IS 

sensors with a 4-20 mA interface. The T5 series can support up 

to 24 inputs (3 modules total including 420IB models with 8 inputs 

each) depending on available space in your console. The 420EXP 

will most likely be used with explosion proof version of the line leak 

pressure transducers at the sites where IS wiring is not available. 

It can also be used with other 4-20 mA sensors located in non-

hazardous area.
Note: Components located in the hazardous area must be an 

explosion proof version and wiring must be enclosed in explosion proof conduits. 

EXP Analog Input Module Specifications

Number of Channels: 8
Loop Power

24 Volts

Internal Resistance

350 ohms