Stud: #8 threaded post – Franklin Fueling Systems T5 Series Fuel Management System Installation Guide User Manual

Page 15

background image

15

Note: The installer must connect the earth ground conductor to the most 

convenient ground terminal as long as it meets local and national codes. 

The earth ground conductor must be 12 AWG (2.1 mm) or larger.

Nut

Stud: #8 threaded post

Lock Washer
Earth Ground Conductor

Enclosure

Cup Washer

Figure B-2 – Ground Stud

Figure B-1 – 110/240 VAC Power and IS Ground Wiring

Power Supply

Module

RUN

ERR

5V

24V

POWER

L1

N/L2

RELAY OUTPUTS

NC1

C1

NO1

NC2

C2

NO2

LOW VOLTAGE INPUTS

IN1

GND

IN2

GND

8

16

14

10

12

6

2

4 COOLER 15A

B

A

N

LIGHTS 10A

TANK 20A

SENTINEL

PUMP #1

2P-20A

3

7

15

13

9

11

5

1

16

02

15

FF

O

OFF

MAIN

3 4

1 2

02

02

FF

O

FF

O

OFF

FF

O

51

FF

O

01

To Ground Stud

12 AWG (2.1 mm) Min.

(Figure B-2)

Redundant Intrinsic Safety Ground

Green Wire,12 AWG (2.1 mm) Min.

Electrical Power Panel

(shown with cover removed)

Neutral

Ground

Bus

- Circuit Assignment Label -

Electrical Power Panel Door

(back side view)

Black (L1-line) Wire, 14 AWG (1.6 mm) Min.

White (L2-neutral) Wire, 14 AWG (1.6 mm) Min.

Green (Gnd-ground) Wire, 12 AWG (2.1 mm) Min.

CU Earth

Ground Rod

See

Figure B-3

for details

See

Figure B-4

for details