Appendix f: 10 amp relay module (10arly), Figure f-2 – positive dispenser shutdown – Franklin Fueling Systems T5 Series Fuel Management System Installation Guide User Manual
Page 21

21
Appendix F: 10 Amp Relay Module (10ARLY)
The 10 Amp Relay Module is a non-intrinsically safe module that has 6
identical Form C output channels. Each channel has a fuse and three
terminals. Each channel can be configured as NO or NC with the power off
by wiring to the appropriate terminals. A T5 console can accommodate up to
18 outputs (6 outputs on up to 3 modules) as space allows. The diagrams
below illustrate two examples of positive shutdown upon alarm conditions.
10ARLY Module
O2
NC2
C2
NO1
NC1
C1
Relay Module disables the
hook signal to the pump
upon alarm conditions.
110/240 VAC
Electrical Panel
Line
Neutral
Switching Current 10A Max.
Switching Power 1500 VA Max.
NO6
NC6
C6
NO5
NC5
C5
NO4
NC4
C4
NO3
NC3
C3
Figure F-1 – Positive Submersible Control Box Shutdown
Note: A valid dispenser hook signal coming from the AC Input Module (shown in Figure D-1) is required for the above
diagram to function as shown.
NO2
NC2
C2
NO1
NC1
C1
NO6
NC6
C6
NO5
NC5
C5
NO4
NC4
C4
NO3
NC3
C3
DISPENSER 1
10 Amp Relay Module disables power to
the dispenser upon alarm conditions.
110/240 VAC
Electrical Panel
Line
Neutral
Line
Neutral
GND
Switching Current 10A Max.
Switching Power 1500 VA Max.
10ARLY Module
Figure F-2 – Positive Dispenser Shutdown
Note: The relay will need to be configured as polarity inverted in order to function correctly in the above diagram.
Note: If a dispenser’s current rating is higher than 10 Amps, use an appropriate isolation relay.
10 Amp Relay Module Specifications
Number of Channels:
6 Form C
Contact Rating:
10A @ 250 VAC
or ½ hp @ 240 VAC
¼ hp @ 120 VAC