Starting Autocal

When Autocal starts, it will need a reference volume as

the starting point for the calibration. The default reference

volume will be what the tank gauge is reading at the

time that Autocal is started. This reading needs to be as

accurate as possible

and not higher than the initial

volume read by the ATG, in order to produce a quality

chart. The Diameter, Length, and Correction Points are

what contribute to the default volume’s accuracy. The

diameter of the tank should be listed on the tank chart, but,

if it’s not, then it can be easily measured.
To begin the Autocal process;

1. Select a tank from the Inventory Summary Screen.

2. After selecting the tank, press the (MENU) key in

the upper right hand corner.

3. Next, select Control/Tanks/Autocalibration.

4. Select the tank and this message should

appear “Are you sure you want to perform the

autocalibration on this tank?” Select OK.